Phase-Coordinate Modeling of Electromagnetic Transients for Fault Analysis in Distribution Networks
Serhii Lebedka, Illia Diahovchenko, Mykhailo Petrovskyi, Vladislav Diachenko
Key points
From the paper's conclusion- The model was implemented in software and evaluated using a 110/6 kV network section of an operating substation, with calculated transients compared with field-recorded oscillograms.
Abstract
Single-line-to-ground (SLG) faults in medium-voltage distribution networks can produce significant capacitive currents and transient overvoltages, particularly in cable-dominated networks with different neutral-grounding arrangements. This study develops a phase-coordinate modeling framework for three-phase distribution networks based on discrete multipole models and the second-order implicit Gear method. Transmission-line sections, transformer windings, and shunt elements are represented in a unified current-based form and assembled into a nodal system. The model was implemented in software and evaluated using a 110/6 kV network section of an operating substation, with calculated transients compared with field-recorded oscillograms. The model reproduced the main features of the measured SLG-fault response, including capacitive-current impulses and transient overvoltages. Arcing faults produced overvoltage factors of 2.1 during arc extinction and 2.4 during subsequent restrikes. Parametric analysis showed that neutral-reactor tuning strongly affects the reactive component of the SLG-fault current and the neutral displacement voltage near resonance. The framework provides a basis for transient analysis, assessment of neutral-grounding measures, and further studies of overcurrent and overvoltage protection.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Coordinated Transient Voltage Support Considering Induction Motor Dynamics in PV-Integrated Distribution Networks Under Symmetrical FaultsSymmetry · 2026
- A Non-Pilot Accelerated Distance Protection Scheme Based on RCBO for SLG Faults on IBR-Connected Transmission LinesEnergies · 2026
- Seismic resilience evaluation of power engineering structures considering near-fault ground motion effectEngineering Research Express · 2026
- Review of Neutral Grounding Modes, Resistor Monitoring, and Methodology for Transitioning to Resistive Grounding in 6–10 kV Distribution NetworksApplied Sciences · 2026
- Fault Location on Series-Compensated Transmission Lines Using Incremental Quantities and Emulating a Nonlinear Metal-Oxide VaristorElectricity · 2026
- Advanced Reactance Method - A Novel Approach for Distance Protection in Presence of Grid-Following Inverter-Based-ResourcesarXiv · 2026