From the paper's conclusion- The results show the performance of the staged formulation on the available records while indicating the need for broader field and electromagnetic-transient validation before generalization to other compensation levels, MOV characteristics, and fault-resistance conditions.
Abstract
This paper presents a staged two-terminal fault-location method for transmission lines with series compensation, based on incremental quantities and a least-squares error (LSE) formulation. The fault distance is first established through an analytical estimator with a bounded linear capacitive correction. This distance is subsequently held fixed during subsample time alignment and the emulation of the nonlinear capacitor and metal-oxide varistor (MOV), thereby preventing the later correction stages from shifting the fault location solely to reduce the fitting residual. Among the 18 paired Common Format for Transient Data Exchange (COMTRADE) records, 10 cases corresponded to the reference distance category, including seven instances with series compensation and three instances without compensation. For these 10 records, the proposed procedure achieved a mean absolute error of 2.26 km, with eight cases within 5 km; excluding the record used during method development, it was 2.48 km, with seven of nine within 5 km. For the compensated subset, the mean absolute error decreased from 4.44 km (raw LSE) to 3.04 km (from 3.94 to 3.50 km excluding that record), whereas the uncompensated subset yielded 0.43 km. Sensitivity and stress analyses quantify the influence of the incremental delay and delimit the applicability of the time-alignment and residual-diagnosis stages. The results show the performance of the staged formulation on the available records while indicating the need for broader field and electromagnetic-transient validation before generalization to other compensation levels, MOV characteristics, and fault-resistance conditions.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Machine Learning and Deep Learning Techniques for Fault Location in Transmission LinesApplied Sciences · 2026
- A Non-Pilot Accelerated Distance Protection Scheme Based on RCBO for SLG Faults on IBR-Connected Transmission LinesEnergies · 2026
- Fault-Section Location System and Strategy for Single-Phase Ground Faults in Flexible-Grounded Distribution NetworksElectronics · 2026
- Phase-Coordinate Modeling of Electromagnetic Transients for Fault Analysis in Distribution NetworksElectronics · 2026
- Multi-Terminal Unsynchronized Fault Location for Distribution Networks Based on MM and SVR–PSO Hybrid OptimizationSymmetry · 2026
- Single-Ended Transmission Line Fault Location Based on Multi-Wavelet Time–Frequency Feature Fusion and a Residual Neural NetworkElectronics · 2026