A Non-Pilot Accelerated Distance Protection Scheme Based on RCBO for SLG Faults on IBR-Connected Transmission Lines
Xiaokai Wang, Anqi He, Shangwen Li, Qian Xu
Key points
From the paper's conclusion- Across 540 PSCAD/EMTDC fault scenarios covering six system configurations, the maximum fault-location error was 1.98%; all 270 tested internal faults within the prescribed acceleration range were successfully accelerated, and all 270 external faults were correctly blocked.
Abstract
High-resistance single-line-to-ground (SLG) faults on inverter-based resource (IBR)-connected transmission lines can cause severe underreach of distance protection because the limited and control-dependent IBR fault current increases the influence of fault resistance on the measured apparent impedance. Consequently, the local Zone-II element may fail to pick up, preventing conventional pickup-dependent acceleration from being initiated. This paper proposes a non-pilot accelerated distance protection scheme for SLG faults that requires neither interstation communication nor local Zone-II pickup. Following remote single-pole opening, the fault-sequence current is reconstructed from the open-pole condition using a segmented nominal-π line model that accounts for line charging. Combining the negative- and zero-sequence boundary equations yields a fault-location residual without an explicit fault-resistance term. The required remote-system source impedance is updated from locally stored prefault phasors, subject to numerical and physical validity checks. Candidate open-pole residuals, a fault-location stability criterion, and a boundary safety margin supervise the acceleration decision. Across 540 PSCAD/EMTDC fault scenarios covering six system configurations, the maximum fault-location error was 1.98%; all 270 tested internal faults within the prescribed acceleration range were successfully accelerated, and all 270 external faults were correctly blocked. The mean post-RCBO trip-decision times ranged from 37 to 45 ms across the six configurations.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Advanced Reactance Method - A Novel Approach for Distance Protection in Presence of Grid-Following Inverter-Based-ResourcesarXiv · 2026
- A transformer-configuration-aware incremental directional protection scheme for inverter-based resourcesFrontiers in Energy Research · 2026
- Power-Swing Blocking Scheme Based on Continuous and Higher-Order Incremental Quantities for Systems with Inverter-Based ResourcesarXiv · 2026
- Power-Swing Blocking and Out-of-Step Tripping Scheme Using the Swing Center Voltage in Systems With Inverter-Based ResourcesarXiv · 2026
- Fault-Section Location System and Strategy for Single-Phase Ground Faults in Flexible-Grounded Distribution NetworksElectronics · 2026
- An Adaptive Injection-Based Protection Method for Distribution Networks Considering Impacts of High-Penetration Distributed GenerationSustainability · 2026