Seismic resilience evaluation of power engineering structures considering near-fault ground motion effect
Liang Cheng, Wanchen Meng, Yanhui Liu
Key points
From the paper's conclusion- This study assesses the seismic resilience of a 220 kV building-equipment system using a coupled finite-element model subjected to 15 ordinary ground-motion (OGM) records and 15 NFGM records.
Abstract
Near-fault ground motion (NFGM) can damage substation buildings and electrical equipment, disrupting equipment operation and delaying access for repair. However, the implications of joint building-equipment damage for post-earthquake functional recovery remain insufficiently understood. This study assesses the seismic resilience of a 220 kV building-equipment system using a coupled finite-element model subjected to 15 ordinary ground-motion (OGM) records and 15 NFGM records. Joint building-equipment damage states, incorporating building-dependent constraints on equipment operation and repair access, are retained for each record to simulate the post-earthquake functional recovery. For the selected records, NFGM generally produces higher fragility for the building, electrical cabinets, and transformers, whereas capacitor banks show no consistent increase. At a peak ground acceleration (PGA) of 0.2 g, the empirical probability of moderate-or-greater building damage increases from 33.33% under OGM to 100% under NFGM. Relative to OGM, mean initial composite functionality under NFGM is 78.34% lower at 0.2 g and falls to zero at 0.4 and 0.6 g. The corresponding relative reductions in the mean 30-day composite resilience index are 29.77%, 32.87%, and 12.41%, respectively. A comparison with unrestricted equipment operation and repair access further quantifies the influence of building-dependent constraints on recovery. Across all 30 records, these constraints reduce the mean 30-day composite resilience index by 11.29%, 38.31%, and 41.00% at 0.2, 0.4, and 0.6 g, respectively. The findings provide guidance for assessing the seismic resilience of substation systems.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Seismic Fragility of Representative High-Voltage Electrical Equipment Considering Joint Ground-Motion and Material VariabilityApplied Sciences · 2026
- Seismic fragility analysis of NPP cabinets considering high-frequency excitations using an efficient numerical modelNuclear Engineering and Technology · 2026
- Experimental Study of Non-Design-Basis Electromagnetic Interference and the Risk of False Operation of Relay Protection at a 500 kV SubstationApplied Sciences · 2026
- Phase-Coordinate Modeling of Electromagnetic Transients for Fault Analysis in Distribution NetworksElectronics · 2026
- A multi-model probabilistic framework for seismic risk assessment and retrofit planning of electric power networksReliability Engineering & System Safety · 2025
- Seismic Performance and Reinforcement Strategies for ±600 kV Suspended Converter Valves — Part1: Seismic VulnerabilitiesSAE technical papers on CD-ROM/SAE technical paper series · 2026