Journal of Physics: Conference Series

Analysis of grounding characteristics of single-direction extended auxiliary grounding grids for transmission towers

Peng Zhang, Zinan Zheng, Yonglian Tang, Hongbo Yu, Fusheng Shan

Key points

From the paper's conclusion
  • The results show that increasing the extension length improves resistance reduction, but the improvement gradually saturates near the effective current-dissipation length.

Abstract

This paper investigates the grounding characteristics of a single-direction extended auxiliary grounding grid for transmission towers. A calculation framework is established using grounding resistance, shunt coefficient, and resistance-reduction efficiency as evaluation indices. The effects of extension length, number of extension leads, terminal structure, soil resistivity, current frequency, and grounding material are evaluated using simulation data. The results show that increasing the extension length improves resistance reduction, but the improvement gradually saturates near the effective current-dissipation length. For 1000 Ω·m soil, the resistance-reduction efficiency increases by 17.56 percentage points when the extension length increases from 30 m to 60 m, whereas it increases by only 2.94 percentage points from 150 m to 180 m. Increasing the number of extension leads further improves current dispersion, especially under power-frequency conditions. Graphite grounding materials also show better high-frequency resistance-reduction performance than galvanized steel. The analysis provides a basis for auxiliary grounding-grid design and for interpreting grounding inspection results in transmission-tower grounding systems.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers