Journal of Physics: Conference Series

Research on corrosion detection criteria for tower grounding grids based on corrosion characteristics and magnetic field response

Zinan Zheng, Peng Zhang, Weibin Ou, Weihua Chen, Yao Tong

Key points

From the paper's conclusion
  • As soil pore saturation increases from 20% to 70%, corner corrosion current density rises markedly.

Abstract

This paper develops a corrosion simulation model for tower grounding grids to analyze corrosion mechanisms, corrosion-prone regions, material differences, and the electromagnetic detection basis. Chemical, electrochemical, stress, and microbiologically influenced corrosion in soil are examined, showing that corrosion reduces conductor cross-section, increases resistance, and changes current distribution. A full-scale finite-element model is built, with soil pore saturation used to describe changes in soil resistivity and oxygen diffusion. Corrosion rates under different locations, materials, and damage conditions are calculated, and the applicability of electromagnetic detection is discussed based on surface magnetic-field variations. Results show that corrosion is more severe at grid corners and extension ends, while frame corrosion is higher at both ends and lower in the middle. As soil pore saturation increases from 20% to 70%, corner corrosion current density rises markedly. Galvanized steel and low-carbon steel are more sensitive to soil moisture, whereas flexible graphite and copper-clad steel have better corrosion resistance. This study provides guidance for corrosion-state identification, detection-path design, and grounding-grid maintenance.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers