Fault Response and Spatial Grounding Current Distribution Characteristics of Multipoint-Grounded GIL-Overhead Line Hybrid Transmission Systems Under High-Resistivity Soil Conditions
Xiaobin Wei, Ming Liang, Yu Fang, Yan Fan, Xiaofei Ding, Xueqin Zhang
Key points
From the paper's conclusion- The results indicate that increased grounding impedance aggravates lightning-induced transient overvoltage.
Abstract
The transient responses of GIL-overhead line hybrid transmission systems during lightning and short-circuit faults directly affect insulation performance, equipment thermal stability, and grounding safety, particularly under high-resistivity soil conditions. However, research on enclosure fault current distribution and its spatial distribution of grounding currents along multipoint-grounded GIL systems under such conditions remains limited. To address this issue, an electromagnetic transient model of a 500 kV GIL-overhead line hybrid transmission system is established to investigate fault responses in high-resistivity soil conditions. The effects of short-circuit types, fault locations, and enclosure grounding spacing on grounding current distribution are analyzed. The results indicate that increased grounding impedance aggravates lightning-induced transient overvoltage. Under short-circuit faults, grounding currents along the GIL exhibit a U-shaped distribution, characterized by higher currents at both ends and lower currents in the middle. The peak local grounding current reaches 42.22 kA during a single-phase-to-ground fault in the middle section of the GIL. This study provides a basis for identifying critical grounding points, selecting adverse fault conditions, and comparing grounding configurations in hybrid transmission systems, as well as for grounding-lead thermal stability verification and grounding safety assessment.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Transient Characteristics Analysis and Resistance Reduction Optimization of Tower Grounding Electrodes Based on Non-Uniform Transmission Line Impedance ModelEnergies · 2026
- Analysis of the Implementation of Effective Grounding in 400 kV Overhead LinesEnergies · 2026
- Analysis of grounding characteristics of single-direction extended auxiliary grounding grids for transmission towersJournal of Physics: Conference Series · 2026
- Modeling and Analysis of Slope-Dependent Response Properties of Gas-Insulated Transmission Line System Under Vehicle-Induced LoadsEng · 2026
- Impulse Effective Length of Horizontal Grounding Electrodes for 220 kV Transmission Towers Under Different Soil ConditionsEnergies · 2026
- Bypass Sheath Voltage Limiters at Cable-to-GIS Terminations: Geometry-Resolved Connection-Lead Impedance for Insulation Coordination Under Very Fast Transient OvervoltagesEnergies · 2026