Optimization of lightning protection grounding devices for distribution line towers under limited construction area
Lin Chen, Shutao Cai, Changhong Lin, Shaoling Hong, Lize Tang, Xiaodong Xu
Key points
From the paper's conclusion- The study provides a practical, compact grounding route for distribution towers where construction space is more critical than conductor length alone.
Abstract
Distribution line towers installed in dense urban corridors, mountain slopes, and narrow roadside corridors are often restricted by small excavation areas, poor equipment access, and uncertain soil conditions. Conventional long horizontal grounding electrodes may therefore be difficult to install, while short vertical rods may be sensitive to soil layering and seasonal moisture. This paper proposes a compact grounding method for distribution line towers under limited construction area conditions. The method combines site-constraint classification, equivalent resistance calculation, numerical comparison of horizontal, vertical, and composite electrodes, and structure-parameter optimization. Analytical formulas for single electrodes are used to define the initial design space, and a numerical experiment is then built for 10 kV and 35 kV distribution tower applications. Results show that, under a 10 m 2 construction area and 200 Ω·m soil resistivity, the optimized compact composite method reduces the calculated grounding resistance from 23.6 Ω for a horizontal arrangement to 11.8 Ω. The proposed design also improves installation adaptability by placing short horizontal conductors near the tower base and adding vertical rods at electrically effective nodes. The study provides a practical, compact grounding route for distribution towers where construction space is more critical than conductor length alone.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Transient Characteristics Analysis and Resistance Reduction Optimization of Tower Grounding Electrodes Based on Non-Uniform Transmission Line Impedance ModelEnergies · 2026
- Impulse Effective Length of Horizontal Grounding Electrodes for 220 kV Transmission Towers Under Different Soil ConditionsEnergies · 2026
- Analysis of the Implementation of Effective Grounding in 400 kV Overhead LinesEnergies · 2026
- Analysis of grounding characteristics of single-direction extended auxiliary grounding grids for transmission towersJournal of Physics: Conference Series · 2026
- Full-process evaluation of lightning protection for multi-circuit 10 kV distribution linesJournal of Physics: Conference Series · 2026
- Bypass Sheath Voltage Limiters at Cable-to-GIS Terminations: Geometry-Resolved Connection-Lead Impedance for Insulation Coordination Under Very Fast Transient OvervoltagesEnergies · 2026