Transient Characteristics Analysis and Resistance Reduction Optimization of Tower Grounding Electrodes Based on Non-Uniform Transmission Line Impedance Model
Yong He, Longjie Wu, Donghui Nie, Haiao Tan, Lin Lu, Guote Liu
Key points
From the paper's conclusion- These results quantify the applicable benefit and saturation tendency of the proposed retrofit while limiting the experimental validation to the tested negative-polarity condition.
Abstract
The impulse response of a transmission line tower grounding device governs tower ground potential increase, and consequently affects the back-flashover risk. Conventional estimates based on power frequency grounding resistance and an impulse coefficient do not resolve wave propagation along the electrode or nonlinear soil ionization. This study develops a non-uniform transmission line model for horizontal tower grounding electrodes and uses it to evaluate a short conductor resistance reduction scheme. The model combines transmission line current division, a multi-wave impedance tower representation, and a segmented π-type grounding network. The shunt conductance and capacitance of each segment are updated by successive approximation from the local dispersed current and the critical soil electric field. For a 30 m benchmark electrode, the calculated impulse resistance is 45.24Ω as compared with 44.98Ω from CDEGS, corresponding to a deviation of 0.58%. A full-scale field test on a 220 kV tower under a negative-polarity 8/20μs impulse gives measured and simulated impulse resistances of 3.35Ω and 3.15Ω, respectively, with a relative error of 5.97%. The validated modeling procedure is then applied in CDEGS/HIFREQ to an 8 m square frame with four 30 m radial electrodes. Adding 6 m short conductors reduces the impulse resistance by 19.49%, 13.76%, and 9.55% at 10, 50, and 100 kA, respectively; increasing the number of short conductors produces diminishing incremental reductions. These results quantify the applicable benefit and saturation tendency of the proposed retrofit while limiting the experimental validation to the tested negative-polarity condition.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Impulse Effective Length of Horizontal Grounding Electrodes for 220 kV Transmission Towers Under Different Soil ConditionsEnergies · 2026
- Optimization of lightning protection grounding devices for distribution line towers under limited construction areaJournal of Physics: Conference Series · 2026
- Analysis of the Implementation of Effective Grounding in 400 kV Overhead LinesEnergies · 2026
- Full-process evaluation of lightning protection for multi-circuit 10 kV distribution linesJournal of Physics: Conference Series · 2026
- Analysis of grounding characteristics of single-direction extended auxiliary grounding grids for transmission towersJournal of Physics: Conference Series · 2026
- Fault Response and Spatial Grounding Current Distribution Characteristics of Multipoint-Grounded GIL-Overhead Line Hybrid Transmission Systems Under High-Resistivity Soil ConditionsProcesses · 2026