Electric Field Distortion Under Transient Electro-Thermal Stresses in LCC-HVDC Valve Side Bushings with Spring Contact Defects
Gwan Hyeok Kim, Yu Jin Kwahk, Jong Geon Lee, Bang Wook Lee
Key points
From the paper's conclusion- Conversely, contact defects caused an electric field inversion: the final-layer field surged by 122.3% (from 1.39 to 3.09 kV/mm) at 937 h, exceeding the first layer (1.05 kV/mm) by 2.04 kV/mm, and remained inverted at 8640 h (2.97 vs.
Abstract
The long-term operational reliability of a valve-side bushing in High-Voltage Direct Current (HVDC) converter transformers depends heavily on the integrity of the spring contact. The existing literature has primarily focused on static defects under steady-state conditions. This study analyzes time-dependent temperature and electric field characteristics under both normal and spring contact defect conditions using a time-varying model accounting for harmonic-induced heating and temperature-dependent conductivity. Harmonic components were derived from operational waveforms of the Bukdangjin LCC-HVDC converter transformer valve-side bushing. Over an 8640 h simulation reaching a maximum contact hot-spot temperature of 107.789 °C, results revealed that under normal conditions, the radial field temporarily flattened at 937 h, with the gap between the first and final layers narrowing by 86.7% (from 2.593 to 0.345 kV/mm) before recovering at a steady state. Conversely, contact defects caused an electric field inversion: the final-layer field surged by 122.3% (from 1.39 to 3.09 kV/mm) at 937 h, exceeding the first layer (1.05 kV/mm) by 2.04 kV/mm, and remained inverted at 8640 h (2.97 vs. 2.14 kV/mm). Consequently, these findings demonstrate that bushing insulation experiences the most severe electro-thermal stress during the transient state, where contact-induced temperature gradients govern dielectric stress intensification at the outermost layers.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Influence of semiconductive shielding protrusions on the electric field distribution in ±500 kV HVDC cables.PloS one · 2026
- Overheating Characteristics of Contact Defects in the Transition Circuit of Oil-immersed Power Transmission Equipment On-Load Tap ChangerEngineering Research Express · 2026
- Transient Temperature Rise and Grounding Characteristics of Vertical DC Grounding Electrodes Considering Soil Electro-Thermal CouplingEnergies · 2026
- Transient Electric Field Evolution in a 220 kV Cable Joint Under Switching Overvoltage Considering Measured Dielectric DispersionProcesses · 2026
- Investigation on Electromagnetic–Thermal–Mechanical Multi-Physics Field Characteristics of GIS Disconnector Under Different Contact ConditionsEnergies · 2026
- Electrothermal Failure Mechanism of Multi-Finger Contacts in a Disconnector Under Foundation-Induced DisplacementEnergies · 2026