From the paper's conclusion- To address this critical issue, this study establishes a bidirectional dynamic electro-thermal coupled model for a vertical grounding electrode using COMSOL Multiphysics.
Abstract
The continuous current dissipation of direct current grounding electrodes generates intense Joule heat, causing severe soil moisture loss and localized thermal runaway. Traditional static models ignore the temperature-dependent nature of soil parameters, leading to dangerous underestimations of actual temperature rises and thermal risks. To address this critical issue, this study establishes a bidirectional dynamic electro-thermal coupled model for a vertical grounding electrode using COMSOL Multiphysics. Comparative analysis demonstrates that the dynamic model accurately reproduces the late-stage accelerated temperature rise observed in experiments, proving its necessity over static methods. Simulations reveal that increased soil resistivity governs heat generation and directly causes a dramatic surge in both grounding resistance and maximum step voltage. In two-layer heterogeneous soils, current is forced into lower-resistivity regions, triggering extreme localized overheating. To mitigate this, expanding the cross-sectional radius of the coke bed effectively suppresses the thermal concentration. These findings provide quantitative evidence and non-uniform design guidelines for the safe operation and thermal protection of grounding electrodes under complex geological conditions.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Electric Field Distortion Under Transient Electro-Thermal Stresses in LCC-HVDC Valve Side Bushings with Spring Contact DefectsEnergies · 2026
- Impulse Effective Length of Horizontal Grounding Electrodes for 220 kV Transmission Towers Under Different Soil ConditionsEnergies · 2026
- Effect of Layered Backfill Soil Saturation on Ampacity of Direct-Buried Cables and a Graded Control StrategyApplied Sciences · 2026
- Improving the Measurement Accuracy of HVDC Grounding Impedance Under Multilayer Soil Uncertainty for Energy Engineering ApplicationsAlgorithms · 2026
- Analysis of the Implementation of Effective Grounding in 400 kV Overhead LinesEnergies · 2026
- Derivation of Equivalent Soil Thermal Resistivity for EHVDC Cable Design in Layered Offshore Seabed ConditionsEnergies · 2026