Transient Electric Field Evolution in a 220 kV Cable Joint Under Switching Overvoltage Considering Measured Dielectric Dispersion
Yanzhi Wu, Junping Cao, Xing Li, Shaohua Wang, Fan Yang, Yinan Jiang, Yonghe Zhou, Zikang Yang
Key points
From the paper's conclusion- The results identify the inner shielding-tube termination as the dominant field-concentration region and establish a reproducible link between measured dielectric dispersion and transient-field analysis.
Abstract
Switching energization imposes wideband transient voltages on cable joints, whereas conventional simulations often use frequency-independent properties for semiconductive field-control components. This study develops a measurement-informed time-domain workflow for a 220 kV cable joint. A 13.976 km route containing 31 joints was evaluated at 20 closing angles, yielding a maximum positive overvoltage of 493.65 kV at 90°. Full-spectrum analysis placed 99.67% of the Hann-windowed record energy at or below 20 kHz, supporting dielectric measurements over 10–20 kHz. At 25 °C, the relative permittivity, polarization-loss tangent, and DC conductivity of semiconductive silicone rubber were measured. One- to six-pole Debye models were compared, and a five-pole representation was selected using the minimum Bayesian information criterion, with a combined weighted relative root-mean-square error of 8.17%. The causal model was implemented in a two-dimensional time-dependent electric-currents model for the stress-control cones and the inner and outer semiconductive shielding layers. A whole-domain search located the global maximum, 12.82 kV/mm at 6.90 ms, at the inner shielding-tube termination; the stress-cone-adjacent insulation reached 5.67 kV/mm at 8.80 ms. The results identify the inner shielding-tube termination as the dominant field-concentration region and establish a reproducible link between measured dielectric dispersion and transient-field analysis.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Effects of Thermal Cycling on the Partial Discharge Characteristics of Epoxy–Metal Interfaces in Cable AccessoriesPolymers · 2026
- Simulation-Based Ampacity Assessment of Cable Joints Based on Hotspot-Temperature InversionElectronics · 2026
- Extraction of cable dielectric parameters and degradation characterization based on broadband reflection coefficient spectraMeasurement Science and Technology · 2026
- Electric Field Distortion Under Transient Electro-Thermal Stresses in LCC-HVDC Valve Side Bushings with Spring Contact DefectsEnergies · 2026
- Frequency-Dependent Surface-Discharge Lifetime and PRPD Failure Signatures of Polyimide Insulation Under High-Frequency Sinusoidal Voltage.Polymers · 2026
- Investigation on Electromagnetic–Thermal–Mechanical Multi-Physics Field Characteristics of GIS Disconnector Under Different Contact ConditionsEnergies · 2026