Overheating Characteristics of Contact Defects in the Transition Circuit of Oil-immersed Power Transmission Equipment On-Load Tap Changer
Jiahao Li, Hua Yu, Hong Liu, Shuaibiao Zeng, Jiayi Guo
Key points
From the paper's conclusion- The results can provide a reference for assembly quality control and overheating-defect diagnosis of transition circuits in oil-immersed power transmission equipment OLTCs.
Abstract
To address the local overheating and ablation problems of fastening connection structures in the transition circuit of oil-immersed power transmission equipment on-load tap changers (OLTCs), this paper proposes a contact-defect simulation method based on Joule-heating energy equivalence. According to the short-duration high-current characteristics during tap-changing operation, the current-carrying process of the transition circuit is equivalently converted into a laboratory current-carrying condition of 258 A for 2 s. A temperature-rise test platform consisting of a programmable AC constant-current source, prototype connection specimens, and an infrared thermal imager is established. Typical contact-defect conditions, including insufficient tightening torque, foreign-particle inclusion, abnormal anti-loosening coating, and uneven contact end surfaces, are designed to investigate the temperature-rise characteristics of the connection structure. The experimental results show that contact defects change the contact state of the conductor-connector interface, reduce the real contact area, increase the contact resistance, and intensify local temperature rise. Furthermore, an electro-thermal coupled simulation model is developed, in which an equivalent contact heat flux is used to characterize the additional interfacial heating caused by contact degradation. The results show that when the equivalent contact heat flux increases from 1.0×105 W/m2 to 1.0×106 W/m2, the simulated additional temperature rise increases from 9.07 ℃ to 103.06 ℃, which is consistent with the experimental trend that contact defects lead to increased temperature rise. The results can provide a reference for assembly quality control and overheating-defect diagnosis of transition circuits in oil-immersed power transmission equipment OLTCs.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Investigation on Electromagnetic–Thermal–Mechanical Multi-Physics Field Characteristics of GIS Disconnector Under Different Contact ConditionsEnergies · 2026
- Electric Field Distortion Under Transient Electro-Thermal Stresses in LCC-HVDC Valve Side Bushings with Spring Contact DefectsEnergies · 2026
- Simulation-Based Ampacity Assessment of Cable Joints Based on Hotspot-Temperature InversionElectronics · 2026
- Electrothermal Failure Mechanism of Multi-Finger Contacts in a Disconnector Under Foundation-Induced DisplacementEnergies · 2026
- Edge-localization damage mechanism in electrical contact at the micro-asperity scaleCell Reports Physical Science · 2026
- Study on phase-change melting characteristics of rigid catenary wires under dynamic separation processTransportation Safety and Environment · 2026