Fault Detection with Weak Electrical Signatures in Grid-Connected Distributed PV Systems Using Positive-to-Negative-Sequence Perturbation Responses

Peng Chang, Rong Sun, Yuyang Tian, Zhixiang Zou, Chenwen Cheng

Key points

From the paper's conclusion
  • Furthermore, robustness evaluations verify reliable detection of the representative 10 Ω fault down to a 20 dB target-frequency SNR under a fixed 14.5 dB anti-noise threshold, while explicitly quantifying the selectivity and sensitivity trade-offs under non-fault switching, channel mismatch, and the reduced kilohm-range sensitivity caused by the elevated anti-noise threshold.

Abstract

Inverter current control can significantly weaken power-frequency fault signatures in distribution networks with high photovoltaic (PV) penetration. This paper proposes an active fault detection method using positive-to-negative-sequence perturbation responses. A small-signal positive-sequence voltage is injected on the low-voltage side of the PV step-up transformer, and the target-frequency ratio of negative-sequence voltage to positive-sequence current (Knp = Vn/Ip) measured at the medium-voltage point of common coupling (PCC) quantifies the resulting cross-sequence coupling response. Sequence-domain analysis combined with nodal admittance reduction explains the off-diagonal coupling terms introduced by single-phase ground and series faults and extends the observation principle to intermittent arcing faults. Sliding-window phasor estimation, a calibrated and locked normal-operation baseline, and consecutive confirmation form the online protection criterion. Co-simulation demonstrates a 13.133–22.638 dB index change across 650–850 Hz and a 37.43–43.35 dB separation between healthy and faulted states across the tested operating and grid strength variations. A 32-point fault resistance sweep characterizes the baseline-crossing mechanism responsible for the intermediate magnitude–sensitivity gap near 3.68 kΩ and verifies detection recovery up to 24 kΩ under the nominal 3 dB threshold. RT-Box real-time tests confirm online trip generation within 20 ms for all three fault types. Furthermore, robustness evaluations verify reliable detection of the representative 10 Ω fault down to a 20 dB target-frequency SNR under a fixed 14.5 dB anti-noise threshold, while explicitly quantifying the selectivity and sensitivity trade-offs under non-fault switching, channel mismatch, and the reduced kilohm-range sensitivity caused by the elevated anti-noise threshold.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

Fault Detection with Weak Electrical Signatures in Grid-Connected Distributed PV Systems Using Positive-to-Negative-Sequence Perturbation Responses — Science Skim