Fault Detection with Weak Electrical Signatures in Grid-Connected Distributed PV Systems Using Positive-to-Negative-Sequence Perturbation Responses
Peng Chang, Rong Sun, Yuyang Tian, Zhixiang Zou, Chenwen Cheng
Key points
From the paper's conclusion- Furthermore, robustness evaluations verify reliable detection of the representative 10 Ω fault down to a 20 dB target-frequency SNR under a fixed 14.5 dB anti-noise threshold, while explicitly quantifying the selectivity and sensitivity trade-offs under non-fault switching, channel mismatch, and the reduced kilohm-range sensitivity caused by the elevated anti-noise threshold.
Abstract
Inverter current control can significantly weaken power-frequency fault signatures in distribution networks with high photovoltaic (PV) penetration. This paper proposes an active fault detection method using positive-to-negative-sequence perturbation responses. A small-signal positive-sequence voltage is injected on the low-voltage side of the PV step-up transformer, and the target-frequency ratio of negative-sequence voltage to positive-sequence current (Knp = Vn/Ip) measured at the medium-voltage point of common coupling (PCC) quantifies the resulting cross-sequence coupling response. Sequence-domain analysis combined with nodal admittance reduction explains the off-diagonal coupling terms introduced by single-phase ground and series faults and extends the observation principle to intermittent arcing faults. Sliding-window phasor estimation, a calibrated and locked normal-operation baseline, and consecutive confirmation form the online protection criterion. Co-simulation demonstrates a 13.133–22.638 dB index change across 650–850 Hz and a 37.43–43.35 dB separation between healthy and faulted states across the tested operating and grid strength variations. A 32-point fault resistance sweep characterizes the baseline-crossing mechanism responsible for the intermediate magnitude–sensitivity gap near 3.68 kΩ and verifies detection recovery up to 24 kΩ under the nominal 3 dB threshold. RT-Box real-time tests confirm online trip generation within 20 ms for all three fault types. Furthermore, robustness evaluations verify reliable detection of the representative 10 Ω fault down to a 20 dB target-frequency SNR under a fixed 14.5 dB anti-noise threshold, while explicitly quantifying the selectivity and sensitivity trade-offs under non-fault switching, channel mismatch, and the reduced kilohm-range sensitivity caused by the elevated anti-noise threshold.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- A New Current Fingerprinting Sensing Method for Adaptive Protection of PV-Integrated Distribution Networks.Sensors (Basel, Switzerland) · 2026
- Coordinated Transient Voltage Support Considering Induction Motor Dynamics in PV-Integrated Distribution Networks Under Symmetrical FaultsSymmetry · 2026
- A Recording-Trigger Method for DC-Side Insulation Anomalies of Photovoltaic Inverters Under Wide-Range Voltage FluctuationsEnergies · 2026
- Current Distortion Mechanisms in Two-Stage Three-Phase Photovoltaic Inverters Under Asymmetric Voltage SagsElectronics · 2026
- A Non-Pilot Accelerated Distance Protection Scheme Based on RCBO for SLG Faults on IBR-Connected Transmission LinesEnergies · 2026
- An Adaptive Injection-Based Protection Method for Distribution Networks Considering Impacts of High-Penetration Distributed GenerationSustainability · 2026