A New Current Fingerprinting Sensing Method for Adaptive Protection of PV-Integrated Distribution Networks.
Ahmed A Salem, Emad Eldeen Omran, Azza A ElDesouky, Hany S E Mansour, Mohamed A A Mohamed, Eyad S Oda
Department of Electrical Engineering, Faculty of Engineering, Suez Canal University, Ismailia 41522, Egypt. · Suez Canal Authority, Ismailia 41522, Egypt.
Key points
From the paper's conclusion- The same fault types are then verified at three fault locations on a practical Egyptian 11 kV feeder model, where the sensing layer is confirmed on an electromagnetic transient (EMT) model and the scheme removes the violations of single-setting coordination using an estimated 4 kB of relay memory.
Abstract
Grid-following photovoltaic (PV) inverters inject fault currents whose magnitude and phase are set by the control mode active during the disturbance, so directional overcurrent relay (DOCR) settings coordinated for one inverter response can miscoordinate after a mode change. This paper proposes a communication-free adaptive protection scheme built on local sensing. A voltage-adaptive current fingerprinting classifier uses local positive sequence measurements to detect current-limiting (CL), active current priority (ACP) and reactive current priority (RCP) operation, as well as momentary cessation (MC) and asymmetrical faults. The classifier activates the relay setting group prepared offline for the detected mode. With pickup currents fixed, the coordination sub-problem is shown to be a linear program (LP), so every setting group is computed at its exact global optimum. Where the grid code droop law makes ACP and RCP indistinguishable by angle, the classifier declares the ambiguity and activates a group that is feasible for both. Under a class-0.5 instrument transformer noise model, the group placed in service is coordination-valid in 99.8% of cases and the expected residual miscoordination is 3.0×10-5 s, 0.01% of the 0.30 s margin. On the CIGRE medium-voltage benchmark, the scheme satisfies the margin in all operating modes for three-phase, line-to-line (LL) and single-line-to-ground (SLG) faults. The same fault types are then verified at three fault locations on a practical Egyptian 11 kV feeder model, where the sensing layer is confirmed on an electromagnetic transient (EMT) model and the scheme removes the violations of single-setting coordination using an estimated 4 kB of relay memory.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Output-Interval-Indexed Adaptive Pickup Current Settings for Inverse-Time Overcurrent Protection in Distribution Networks with High Shares of Inverter Interfaced Renewable GenerationSustainability · 2026
- Fault Detection with Weak Electrical Signatures in Grid-Connected Distributed PV Systems Using Positive-to-Negative-Sequence Perturbation ResponsesElectronics · 2026
- Transferable Neuromorphic Protection for Distribution NetworksarXiv · 2026
- Voltage-Supervised Inverse-Time Overcurrent Protection Coordination with Scenario-Based Setting Groups for Inverter-Dominated MicrogridsEnergies · 2026
- An Overview of Anti-Islanding Protection Schemes in PV-Based MicrogridsEnergies · 2026
- Adaptive Overcurrent Protection of Distribution Substations with Definite-Time CharacteristicsEnergies · 2026