Current Distortion Mechanisms in Two-Stage Three-Phase Photovoltaic Inverters Under Asymmetric Voltage Sags
Ahmad Alzahrani
Key points
From the paper's conclusion- This study models a 10 kW, 700 V inverter with an LCL interface and compares notch filtering, established ripple estimators, and a sampled harmonic predictor of net converter power, each with and without DC duty normalization of the boost stage.
Abstract
Asymmetric grid sags make the DC-link energy of two-stage three-phase photovoltaic inverters pulsate at twice the grid frequency. A DC-voltage regulator acting on this pulsation injects low-order grid-current harmonics. This study models a 10 kW, 700 V inverter with an LCL interface and compares notch filtering, established ripple estimators, and a sampled harmonic predictor of net converter power, each with and without DC duty normalization of the boost stage. Under a 0.4 pu phase-a sag below the current limit, raw feedback produces 3.27% THD. With a 150 Hz source-power feedforward, removing the ripple from the regulator or normalizing the boost duty alone leaves 0.48% or more, while the two together reach 0.027–0.046%. A conventional 5 Hz loop reaches 0.15–0.41%, but recovers slowly from source steps. With a compensated 1 μs dead time, a switched model gives 0.43–0.86% total THD, and coordination cuts the fault-driven third harmonic from 3.9% to 0.075–0.12%. A frequency-adaptive narrow notch matches the predictor’s phase margin and transient within 0.1 A and 0.3 V, holds its distortion over ±1 Hz and frequency ramps, and needs no capacitance identification; the predictor is preferred only where a capacitance estimate is desired. Results cover three sag types, all inception angles, grid strengths down to a short-circuit ratio of 3, negative-sequence injection, and background harmonics, and are checked by Floquet analysis and processor-in-the-loop execution. In a two-board controller hardware-in-the-loop test with device losses and sensor noise in the emulated plant, the complete controller runs in 10.1 μs per 50 μs period and reproduces the co-simulated distortion within 0.02 percentage point in all 65 runs with a digital measurement link.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Power Decoupling of an AC-Side Voltage Sensorless Three-Phase Converter Under Unbalanced Grid ConditionsIEEE Transactions on Power Electronics · 2025
- Active damping and harmonic suppression strategy of LCL Grid-tied inverters based on single inverter-side inductor current feedback considering sampling delayJournal of Physics: Conference Series · 2026
- A Unified Power Calculation Scheme for Single-Phase Droop-Based Inverters Considering the Use of Nonlinear LoadsEnergies · 2026
- Fault Detection with Weak Electrical Signatures in Grid-Connected Distributed PV Systems Using Positive-to-Negative-Sequence Perturbation ResponsesElectronics · 2026
- Design and Control of a High-Gain Converter-Based Grid-Connected PV System for Enhanced Dynamic Performance and LVRT CapabilityEngineering Research Express · 2026
- Bit-Accurate FPGA Current Control of a PV-STATCOM: Delay and Word-Length Limits for Ride-ThroughElectronics · 2026