Electrical Engineering

Power quality impact of residential LED loads under grid and isolated generator supply

Thiago Farias dos Santos, Ana Julia Dal Forno, Cassio Espindola Antunes, Thiago Trentini, Jomar Alberto Andreata

Key points

From the paper's conclusion
  • The results obtained show that under utility grid supply, THD I and THD V increased only slightly, with minor effects on PF .

Abstract

This paper analyzes the impact of residential LED lamp aggregation on low-voltage systems under two supply conditions: (a) connection to the electric utility grid and (b) operation supplied by an isolated synchronous generator. Experimental tests were performed with groups of 9-W lamps, ranging from one to thirty units, supplied by both voltage sources. Total harmonic distortion of current (THD I ), total harmonic distortion of voltage (THD V ), and power factor (PF) were measured. Additionally, a nonlinear model was developed and simulated in ATPDraw to represent its behavior in terms of power quality disturbances. The results obtained show that under utility grid supply, THD I and THD V increased only slightly, with minor effects on PF . In contrast, there was a severe deterioration in power quality when the lamps were supplied by the isolated generator: THD I exceeded 100% and THD V surpassed 20%. Regarding electrical performance, the PF dropped to 0.54 for 30 units. It was observed that the addition of linear resistive loads reduced THD I , under the tested conditions. Simulation results closely matched experimental measurements, confirming the suitability of the proposed model for further studies. This work highlights the vulnerability of isolated systems to nonlinear residential loads, emphasizing that islanded and microgrid systems may be more susceptible to harmonic distortion and degradation of electrical performance.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

Power quality impact of residential LED loads under grid and isolated generator supply — Science Skim