Harmonic Distortion and Distribution Transformer Thermal Risk in Low-Voltage Networks: Feeder Impedance Sensitivity for Sustainable Renewable Energy Integration

Francis Bennie, Mohamed Khan, Andrew Swanson

Key points

From the paper's conclusion
  • The results demonstrate that feeder weakness can materially increase remote-node voltage and harmonic sensitivity without producing a corresponding increase in transformer thermal severity.

Abstract

The increasing penetration of distributed energy resources (DERs) in low-voltage networks is central to the clean energy transition but introduces coupled challenges in voltage regulation, harmonic distortion, and distribution-transformer operation that impact grid sustainability and asset longevity. This paper isolates feeder impedance as a controlled variable and evaluates whether remote-network power-quality severity and transformer consequence follow the same sensitivity trend. A time-domain model used a factory-matched 200 kVA, 11 kV/420 V Dyn11 transformer with 40% DER connected at remote Node S3. The DER current contained prescribed fifth, seventh, eleventh, and thirteenth harmonics, while the LV feeder resistance and inductance were co-scaled from 0.5 to 2.0 pu. Across the DER-connected sweep, Node S3 line-to-line RMS voltage increased from 420.45 V to 428.95 V, and the voltage-rise magnitude increased from 3.03 V to 11.55 V. Selected-order Node S3 VTHD increased monotonically from 1.104% to 1.395%. Baseline-corrected harmonic transfer impedance also increased at every assessed harmonic, supporting a feeder-impedance-driven voltage-response mechanism. In contrast, transformer loading remained within 14.44–14.52%, total transformer loss within 350.26–350.93 W, hot-spot temperature within 38.229–38.246 °C, and common-baseline relative aging within 0.2863–0.2871. The results demonstrate that feeder weakness can materially increase remote-node voltage and harmonic sensitivity without producing a corresponding increase in transformer thermal severity. Network voltage response and transformer consequence should therefore be assessed as related but non-equivalent engineering domains. By separating power quality management from transformer thermal risk, distribution utilities can avoid premature asset replacement, enabling targeted, resource-efficient investments that support sustainable grid planning and long-term renewable integration (SDG 7 and SDG 9).

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

Harmonic Distortion and Distribution Transformer Thermal Risk in Low-Voltage Networks: Feeder Impedance Sensitivity for Sustainable Renewable Energy Integration — Science Skim