  • The findings demonstrate the value of integrating these methods into a procedure to support power quality diagnostics.

Abstract

This paper presents an integrated procedure to support the assessment of power quality at the points of connection of photovoltaic power plants to medium-voltage distribution networks. The study covered 20 power plants in Poland, for which seven-day power quality measurements were conducted, supplemented by measurements of background grid conditions with the installations disconnected. The proposed procedure combines compliance assessment against the requirements of EN 50160 and the applicable IRiESD, a synthetic power quality index, modeling in DIgSILENT PowerFactory, and multivariate analysis using principal component analysis (PCA) and the Isolation Forest algorithm. The results revealed significant discrepancies between the compliance assessments based on the two sets of requirements: 19 out of the 20 power plants met the EN 50160 requirements for harmonics, whereas all installations exceeded the applicable harmonic limits under the IRiESD requirements. Measurements of the grid background confirmed the presence of elevated levels of certain harmonics even when the power plants were disconnected, highlighting the necessity of accounting for grid conditions when interpreting results. Modeling enabled the analysis of harmonic characteristics, while PCA and Isolation Forest facilitated the preliminary identification of installations with atypical harmonic characteristics. The article describes the measurement and computational methodology, presents the results from the measurements, modeling, and multivariate analysis, and concludes with a discussion on the limitations of the proposed approach. The findings demonstrate the value of integrating these methods into a procedure to support power quality diagnostics.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

Integrated Power Quality Assessment of Photovoltaic Plants Using Field and Background Measurements, Network Modeling, and Unsupervised Analysis — Science Skim