Switching Transients and Power Quality of a 500 kWp Photovoltaic System in a Grid-Connected University Microgrid
Sebastian Różowicz, Dominik Zbróg, Artur Pawelec, Jan Pejas
Key points
From the paper's conclusion- We report Class A measurements (105 days in 12 sessions) at the feeder of a 500 kWp PV system in a university microgrid.
Abstract
Photovoltaic (PV) systems of several hundred kilowatts increasingly operate in low-voltage (LV) microgrids, yet field data on their power quality (PQ) and switching are scarce. We report Class A measurements (105 days in 12 sessions) at the feeder of a 500 kWp PV system in a university microgrid. Voltage indices remained within the EN 50160 benchmark limits (weekly 95th percentile total harmonic distortion, THD, ≤3.02%), and THD did not change when the inverters resumed generation. Current THD reached tens of percent at low output, but the total rated-current distortion stayed ≤0.67% (95th percentile). Passive identification from cloud-induced fluctuations gave a robust Thevenin resistance of 12.1 mΩ and a poorly constrained reactance of 8–17 mΩ, implying a PV-induced voltage rise of up to 3.5%. The inverters rode through dips to 0.59 p.u. while injecting balanced reactive current. Opening the PV feeder under load produced the largest deviations: instantaneous peaks of about 1.5 p.u. until the island voltage collapsed 65–85 ms after current interruption. An island frequency above 69 Hz and a residual voltage of up to 1.35 p.u. exceeded the analyser’s specified ranges and are indicative, but they inflated half-cycle root-mean-square values to 2.42 p.u., so waveform-based assessment is required.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- An Overview of Anti-Islanding Protection Schemes in PV-Based MicrogridsEnergies · 2026
- Performance Boundaries of Hybrid Photovoltaic–Battery Inverters Under Dynamic, Unbalanced, and Grid Disturbance ConditionsEnergies · 2026
- Research on Customer-Side Microgrid Inverters for Grid-Connected Non-Export OperationElectronics · 2026
- Power quality impact of residential LED loads under grid and isolated generator supplyElectrical Engineering · 2026
- A Machine Learning-Driven Framework for Voltage Disturbance Mitigation in Dual PV–Grid IntegrationEnergies · 2026
- Transmission and Distribution Co-Simulation Platform for Renewable-Dense Power Systems with High Solar PenetrationSolar · 2026