Power-Swing Blocking and Out-of-Step Tripping Scheme Using the Swing Center Voltage in Systems With Inverter-Based Resources
Henrik Johansson, Qianli Xing, Jaekeun Lee, Ki-Hyun Kim, Nathaniel Taylor, Xiongfei Wang
Key points
From the paper's conclusion- Misoperation of power-swing blocking (PSB) and out-of-step tripping (OST) schemes in distance relays is a critical concern in power systems with increasing penetration levels of inverter-based resources (IBRs).
Abstract
Misoperation of power-swing blocking (PSB) and out-of-step tripping (OST) schemes in distance relays is a critical concern in power systems with increasing penetration levels of inverter-based resources (IBRs). Recently, several papers have studied the impact of IBRs on conventional dual-blinder PSB/OST schemes. They highlight interoperability issues concerning fast power swings and unconventional impedance trajectories, and propose revised relay settings in attempts to deal with the problems. However, the blinder-based PSB methodology suffers from being dependent on the speed of the apparent impedance just as it crosses between the blinders. It is therefore important to consider alternative methods. This paper thoroughly analyzes the characteristics of the swing center voltage (SCV) and the impacts of grid-forming (GFM) and grid-following (GFL) inverters on its local estimation. Then, an SCV-based PSB/OST scheme is proposed, where the main PSB criterion can be tuned from simple system parameters. This is made possible by a separate PSB activation function. The OST scheme uses only one setting and is motivated from the analytical analysis of the SCV with IBRs. Extensive PSCAD/EMTDC simulations verify the performance of the proposed SCV-based PSB/OST scheme and how it overcomes limitations of blinder-based schemes with GFM and GFL inverters.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Power-Swing Blocking Scheme Based on Continuous and Higher-Order Incremental Quantities for Systems with Inverter-Based ResourcesarXiv · 2026
- A Non-Pilot Accelerated Distance Protection Scheme Based on RCBO for SLG Faults on IBR-Connected Transmission LinesEnergies · 2026
- A Protection-Interoperable Fault Ride-Through Control for Grid-Forming InvertersIEEE Transactions on Industrial Electronics · 2025
- Advanced Reactance Method - A Novel Approach for Distance Protection in Presence of Grid-Following Inverter-Based-ResourcesarXiv · 2026
- Real-time EMT assessment of inverter supplementary control based on PCC power sensing for oscillation dampingat - Automatisierungstechnik · 2026
- A transformer-configuration-aware incremental directional protection scheme for inverter-based resourcesFrontiers in Energy Research · 2026