A transformer-configuration-aware incremental directional protection scheme for inverter-based resources
Rui Fan, Abu Shouaib Hasan, Md Samsul Alam
Key points
From the paper's conclusion- Building on this analysis, we develop an incremental focused directional protection scheme that compares each voltage and current sample with its value one cycle earlier.
Abstract
Inverter-based resources (IBRs) supply fault currents that differ fundamentally from those of synchronous generators, challenging conventional protective relays. While prior studies have focused on positive-sequence fault currents, the negative- and zero-sequence responses of IBRs under unsymmetrical faults, and their dependence on transformer winding connections and grounding, remain insufficiently understood. Using real-time electromagnetic transient simulations, we characterize the sequence currents during balanced and unbalanced faults under four transformer winding connections. The positive-sequence current remains below 1.1 p.u., the negative-sequence current stays below 0.07 p.u., and zero-sequence current appears only for ground faults with a grounded Y-connected transformer, leaving conventional protection with little to act on. Building on this analysis, we develop an incremental focused directional protection scheme that compares each voltage and current sample with its value one cycle earlier. Faults are detected from the change ratio of incremental quantities ( K R ) and the maximum absolute incremental angle ( | Δ θ | max ) , and the trip is supervised by a directional condition on the fault-period voltage-current angle, without requiring line impedance data or sequence currents. Simulation results across diverse fault types, transformer connections, and system conditions show that both detection metrics exceeded their thresholds for all tested faults, while load and capacitor switching produced responses well below the thresholds. High-impedance faults up to 400 Ω were detected, and all tested reverse faults were correctly blocked. Compared with conventional phase overcurrent and zero-sequence protection, the proposed scheme provided broader fault coverage across the tested fault types and transformer connections.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Advanced Reactance Method - A Novel Approach for Distance Protection in Presence of Grid-Following Inverter-Based-ResourcesarXiv · 2026
- A Non-Pilot Accelerated Distance Protection Scheme Based on RCBO for SLG Faults on IBR-Connected Transmission LinesEnergies · 2026
- Protection in Inverter-Dominated Grids: Fault Behavior of Grid-Following vs. Grid-Forming Inverters and Mixed Architectures—A ReviewEnergies · 2026
- Protection challenges and solutions on power systems towards 100% inverter-based resources and energy storage systemsarXiv · 2026
- An Innovative Relaying Scheme for Protection of AC Microgrid Feeders Using Incremental Negative Sequence PowerCSEE Journal of Power and Energy Systems · 2026
- Impact of Grid-Forming Inverters on Protective Relays: A Perspective for Current Limiting Control DesignIEEE Transactions on Industrial Electronics · 2025