Real-time EMT assessment of inverter supplementary control based on PCC power sensing for oscillation damping

Leonardo Silveira, Luiza Saydelles, Ramon Rodrigues, Gustavo Marchesan, Adriano Peres, Martin Wolter

Key points

From the paper's conclusion
  • The controller uses a washout and two-stage lead-lag structure, tuned for a dominant 7.7 Hz oscillatory mode identified by FFT analysis, and modulates the inverter active power reference in phase opposition to the oscillation.

Abstract

The increasing penetration of inverter-based resources (IBRs) alters power grid dynamics, reducing inertia and damping. This work evaluates a supplementary Power Oscillation Damping (POD) controller for a power-controlled inverter, based on active power measurements at the Point of Common Coupling (PCC). The controller uses a washout and two-stage lead-lag structure, tuned for a dominant 7.7 Hz oscillatory mode identified by FFT analysis, and modulates the inverter active power reference in phase opposition to the oscillation. Performance is assessed through real-time electromagnetic transient (RTS-EMT) simulation in Typhoon HIL, using a 13.8 kV distribution feeder with a 6 MVA synchronous generator, for short-circuit ratios (SCR) of 3.10, 2.07, and 1.64 under a 10 % load step. The POD has a minor effect at SCR = 3.10, reduces the settling time from over 800 ms to approximately 350 ms at SCR = 2.07, and prevents the loss of stability observed without the controller at SCR = 1.64.

Read the paper