Low-Voltage Ride-Through in AI Data Centers via Coordinated Battery and Computing Load Control
Xiaoyang Wang, Xin Chen, Fang Chen Lin, Prasad Enjeti, Ali Yazdanpanah, Yunzhi Cheng, Shri Abhyankar
Key points
From the paper's conclusion- Three control scenarios are studied: UPS battery support alone, computing load curtailment alone, and the coordinated use of both resources.
Abstract
The ability of large AI data centers to ride through grid voltage sags is critical to power system stability and reliability. This paper frames data center low-voltage ride-through (LVRT) as a DC-link power balance problem. Once the rectifier reaches its current limit, the power drawn from the grid decreases in proportion to the grid voltage. The DC-link capacitor can supply the resulting power deficit only briefly before the DC-link voltage falls low enough to trigger undervoltage protection tripping. To address this issue, this paper proposes effective control strategies for coordinating uninterruptible power supply (UPS) battery and computing load curtailment to offset the power deficit and enable LVRT at minimum control cost. Three control scenarios are studied: UPS battery support alone, computing load curtailment alone, and the coordinated use of both resources. Electromagnetic transient (EMT) simulations using the TAMU-ERCOT AI data center model demonstrate that battery support and the coordinated strategy achieve LVRT for all tested sags, including a near-zero-voltage fault, while load curtailment alone rides through moderate voltage sags.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Model-Free UPS Control Tuning for Improved Low-Voltage Ride-Through in AI Data CentersarXiv · 2026
- Reducing Data-Center Load Transfers with Ride-Through-Aware Voltage ControlarXiv · 2026
- Voltage Ride-Through-Constrained Power Capping for Large-Scale Data CentersarXiv · 2026
- EMT Modeling and Coordinated Mode-Transition Ride-Through Control of Modern Data CentersarXiv · 2026
- Can STATCOM and UPS-Based Voltage Support Mitigate Fault-Induced Reductions in AI Data Center Grid Power Draw?arXiv · 2026
- Flexible Training Workloads in Large-Scale AI Data Centers for Transient-Stability Support in Transmission-Constrained Power SystemsarXiv · 2026