Model-Free UPS Control Tuning for Improved Low-Voltage Ride-Through in AI Data Centers

Haowen Xu, Xin Chen

Key points

From the paper's conclusion
  • Simulations using the TAMU-ERCOT electromagnetic transient (EMT) AI data center model show that tuning converter control parameters increases the ride-through area by 10.6\%.

Abstract

Voltage sags can trigger protection trips in uninterruptible power supply (UPS) systems, abruptly reducing the power that AI data centers draw from the grid. This paper improves the low-voltage ride-through (LVRT) capability of AI data centers equipped with double-conversion UPS systems by tuning their existing converter controls. We formulate a bound-constrained optimization problem to maximize the ride-through area, defined as the integral of ride-through time over a range of retained grid voltages. To solve this problem, we develop a batched projected zeroth-order optimization algorithm with adaptive moment estimation (BPZO-Adam). The algorithm evaluates candidate control settings using only simulated ride-through times, making it suitable for vendor-supplied black-box models. Simulations using the TAMU-ERCOT electromagnetic transient (EMT) AI data center model show that tuning converter control parameters increases the ride-through area by 10.6\%. In a separate study, tuning the controls yields a larger ride-through area than increasing the DC-link capacitance tenfold.