An IoT-Based Technique for Detecting Single-Phase Earth Faults in 6–35 kV Cable Lines Using Current Sensors
Laura YESMAKHANOVA, Zhanat Issabekov, Bibigul Issabekova, Batyrbek Ordabayev, A Zhantlessova, Dauren Kudabaev, Олжас Талипов
M. Kh Dulati Taraz State University · Toraighyrov University
Abstract
An IoT-based technique is suggested for detecting single-phase earth faults (SEFs) in 6–35 kV cable networks with an isolated neutral. Unlike existing methods based on measuring zero-sequence currents with traditional current transformers, the suggested technique uses a passive magnetically controlled contact (reed switch) placed in the magnetic field of a cable. This enables recording fault currents of 0.5–2.0 A without external power supply and ensures galvanic isolation. The novelty of this technique is the combination of a reed switch current sensor with an IoT platform: instantaneous values of current are measured by the duration of the closed state of the contacts, then the data are transmitted via a radio channel (LoRa 433 MHz, LoRaWAN, or NB-IoT) to a cloud-based SCADA/EMS system for remote monitoring. The amplitude of the current is calculated from the pickup and resetting currents, as well as the duration of the closed state of the contacts; no high-frequency ADC is required. During experimental tests of a prototype with a KEM-5 reed switch and a TZL-10 current transformer, the difference between the calculated and actual protection operation current was no more than 10–5%. Oscillograms confirmed the correct operation of the device when starting, under load, and during an artificial SEF with a current of 1.6 A. The device response time is a fraction of the industrial frequency period, which significantly reduces the emergency mode duration. The suggested system enables decreasing the system average interruption duration index (SAIDI) and the system average interruption frequency index (SAIFI) by selectively disconnecting a damaged section and preventing cascading faults. The use of two independent channels (current transformer and reed switch) increases the reliability of SEF detection and reduces the risk of false operation. Thus, the developed IoT-based technique improves the reliability, safety, and cost-effectiveness of cable network operation.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Fault-Section Location System and Strategy for Single-Phase Ground Faults in Flexible-Grounded Distribution NetworksElectronics · 2026
- Interpretable Fault Diagnosis of Shearer Power-Core Cables from Sensor-Accessible Terminal Electrical Responses.Sensors (Basel, Switzerland) · 2026
- Review of Neutral Grounding Modes, Resistor Monitoring, and Methodology for Transitioning to Resistive Grounding in 6–10 kV Distribution NetworksApplied Sciences · 2026
- A Non-Pilot Accelerated Distance Protection Scheme Based on RCBO for SLG Faults on IBR-Connected Transmission LinesEnergies · 2026
- Restoring CFAR Validity for Single-Channel IoT Sensor Streams: A Monte Carlo Comparison of CFAR-Family and Sequential Detectors Under Cortex-M0+ Constraints.Sensors (Basel, Switzerland) · 2026
- Fault identification method for insulation damage of DC parallel cables in subway systems based on current deviation degreeJournal of Physics: Conference Series · 2026