Fault identification method for insulation damage of DC parallel cables in subway systems based on current deviation degree
Zhou Zhou, Xuetao Liu, Gang Zhang
Key points
From the paper's conclusion- The results show that under normal operating conditions, the current deviation degree of each branch remains at a low level; however, when an insulation damage fault occurs, the deviation degree of the faulty branch increases significantly, enabling effective identification of the faulty cable.
Abstract
To address the difficulty of online and accurate identification of insulation damage faults in multiple parallel cables within urban rail transit DC traction power supply systems, this paper proposes a fault identification method based on the Current Deviation Degree (CDD). This method analyzes the deviation characteristics among branch currents of parallel cables and constructs a current deviation degree index to enable rapid localization of the faulty branch. Meanwhile, a system architecture of “edge acquisition + upper-level recognition” is designed, where multi-channel current synchronous acquisition and data uploading are implemented at the edge side, while deviation degree calculation and fault discrimination are performed on the host computer. A DC 750 V multi-branch parallel cable simulation experimental platform is built to validate the proposed method. The results show that under normal operating conditions, the current deviation degree of each branch remains at a low level; however, when an insulation damage fault occurs, the deviation degree of the faulty branch increases significantly, enabling effective identification of the faulty cable. The findings verify the effectiveness and engineering applicability of the proposed method in online fault detection of DC parallel cables.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Optimized Cable-Armor Blocking for Metro Stray Current Mitigation in Urban Power GridsProcesses · 2026
- Artificial Intelligence Applications in the Process of Power Cable Operation and Maintenance: A Review.Sensors (Basel, Switzerland) · 2026
- Local Faulted-Section Identification for Pole-to-Pole Faults in MVDC Ring Networks Using Hybrid DC Circuit-Breaker Commutation CharacteristicsMachines · 2026
- A Study on Grounding Fault Diagnosis for a 500 kV AC Submarine Cable Using a 1D-CNN–BiLSTM Hybrid Neural Network ModelEnergies · 2026
- Digital twin-driven fault diagnosis of power substations by multi-modal fusion learningNature Communications · 2026
- Fault Detection Methods in a Power Distribution System with DER: A ReviewEnergies · 2026