Energies

Occurrence of a Large Temporary Overvoltage Due to a Phase Interruption in a 220 kV Line

Enrico Maria Carlini, Gaetano Pecoraro, Luigi D’Orazio, Tommaso Bragatto, Fabio Massimo Gatta, Alberto Geri, Stefano Lauria, Marco Maccioni,

Key points

From the paper's conclusion
  • The paper details the occurrence of a severe temporary overvoltage (TOV) in an existing Italian HV/MV system where a radially operated 180 km, 220 kV overhead line experienced an asymmetrical phase conductor break.

Abstract

The paper details the occurrence of a severe temporary overvoltage (TOV) in an existing Italian HV/MV system where a radially operated 180 km, 220 kV overhead line experienced an asymmetrical phase conductor break. The recorded TOV reached 1.43 p.u. (256 kV peak line-to-ground) and 1.41 p.u. (440–445 kV peak line-to-line) at the 220 kV level, transferring a 1.38 p.u. (45 kV peak) overvoltage to the underlying 23 kV MV network and causing customer equipment damage, exceeding standard EHV/HV insulation coordination duration limits. Series faults, liable to cause overvoltages in radial systems, are not uncommon at MV level and have been extensively investigated in the past. Such radial configurations, although much less frequently, can occur also at HV level due to contingencies, maintenance or both. An approximate linear circuit model is presented to explain the underlying series resonance mechanism with the transformer zero-sequence magnetizing impedance. Furthermore, a detailed nonlinear ATP-EMTP system model was developed. Simulation results show excellent quantitative agreement with field recordings (peak error < 2.0%), confirming that transformer core saturation limits the theoretical resonant peak and that local generation restoration effectively suppresses the TOV.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers