Evaluation of the Impact on Transformer Insulation by Lightning Surge Voltage Analysis on Wide‐Area Power Network
Yosuke Ogura, Masanobu Yoshida, Akifumi Yamanaka, Hirokazu Matsumoto
Key points
From the paper's conclusion- As a result of simulations modeling a wide‐area power network, voltages containing frequency components corresponding to the resonance frequency of the transformer neutral point in the range from several to several tens of kHz were confirmed.
Abstract
When lightning surges simultaneously enter three phases of the primary circuit of a transformer, specific frequency components within the lightning surge may match the resonance frequency of the transformer. This can lead to overvoltages at the neutral point of the transformer windings, potentially causing insulation breakdown. In this study, an analysis simulating the entry of the lightning surge into a transformer due to indirect lightning was conducted, and the insulation impact at the transformer neutral point was investigated. As a result of simulations modeling a wide‐area power network, voltages containing frequency components corresponding to the resonance frequency of the transformer neutral point in the range from several to several tens of kHz were confirmed. While it is self‐evident that a direct lightning strike to a transmission tower can lead to transformer failures, it has been suggested that lightning surges occurring in transformers as a result of indirect lightning may also cause transformer failures owing to overvoltages at the transformer neutral point. © 2026 Institute of Electrical Engineers of Japan and Wiley Periodicals LLC.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Integrated Insulation Coordination for Pollution- and Lightning-Exposed Medium-Voltage Distribution NetworksEng · 2026
- Magnetohydrodynamic modelling of high-energy power-frequency arcs in transformer oil: Energy partition and impedance-plasma-property relationshipsJournal of Physics D: Applied Physics · 2026
- Full-process evaluation of lightning protection for multi-circuit 10 kV distribution linesJournal of Physics: Conference Series · 2026
- Bypass Sheath Voltage Limiters at Cable-to-GIS Terminations: Geometry-Resolved Connection-Lead Impedance for Insulation Coordination Under Very Fast Transient OvervoltagesEnergies · 2026
- From Thermal Ablation to Mechanical Fracture: Lightning-Caused Breakage of Insulated Conductors Under Thermal–Mechanical Coupling of Power-Frequency Follow Current ArcsEng · 2026
- Experimental Study of Non-Design-Basis Electromagnetic Interference and the Risk of False Operation of Relay Protection at a 500 kV SubstationApplied Sciences · 2026