A Three-Stage Methodology for Accelerated Monte Carlo Assessment of the Lightning Performance of Large Branched Distribution Networks
Ernesto Pérez, Andrés Osorio, Daniel Aranguren
Key points
From the paper's conclusion- Assessing the lightning performance of real, extensive and highly branched distribution networks is computationally demanding: it requires coupling the electromagnetic field to the line for a large number of Monte Carlo events.
Abstract
Assessing the lightning performance of real, extensive and highly branched distribution networks is computationally demanding: it requires coupling the electromagnetic field to the line for a large number of Monte Carlo events. This paper proposes a three-stage acceleration method that reduces that burden without compromising accuracy. Events are first pre-screened with an analytical estimate, so only the hazardous ones reach a full coupling simulation. The illumination is then bounded to a distance threshold, with the remaining line represented by a frequency-dependent model that preserves the reflections of the branched topology. Finally, for networks that do not fit in a single case, an optional stage partitions the network into sub-networks solved independently and reconstructed. Every threshold is calibrated against a full-fidelity reference on the same strokes, and the values found are offered as a conservative suggestion for this feeder. Two further elements are addressed: an exposure buffer following the network geometry, and a stopping criterion. The method is evaluated on a real 13.2 kV rural feeder of 116 km spanning about 24 km ×24 km, with an exposure area of 178 km2. The acceleration acts on the indirect strokes, the only ones that need the field-to-line coupling; the direct strokes are simulated and reported separately. The computational cost falls by more than one order of magnitude while the error of the exceedance rate of the indirect strokes stays about 1 , and an independent 200,000-stroke campaign confirms statistical consistency. Convergence should be judged from the number of events above the voltage of interest, not from the apparent stabilization of the estimate.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Full-process evaluation of lightning protection for multi-circuit 10 kV distribution linesJournal of Physics: Conference Series · 2026
- Lightning Risk Assessment and Improvement of 110 kV Double-Circuit Transmission Lines on Shared TowersEnergies · 2026
- Spatiotemporal dynamic lightning damage risk assessment for high-altitude distribution lines considering seasonal surface evolution and time-varying lightning withstand capabilityFrontiers in Energy Research · 2026
- Integrated Insulation Coordination for Pollution- and Lightning-Exposed Medium-Voltage Distribution NetworksEng · 2026
- Virtual-Node-Enhanced Mirror-Equivalent Energy Framework for Online Transient Stability Assessment of EHV Transmission LinesProcesses · 2026
- Multi-Terminal Unsynchronized Fault Location for Distribution Networks Based on MM and SVR–PSO Hybrid OptimizationSymmetry · 2026