Lightning Risk Assessment and Improvement of 110 kV Double-Circuit Transmission Lines on Shared Towers

Weixiang Huang, Xiaofei Xia, Yixiong Yang, Chenying Yi, Xi Chen, Zhidu Huang

Key points

From the paper's conclusion
  • This study examines a 110 kV line in Guangxi, China, using lightning monitoring and operational records.

Abstract

A single lightning strike on a double-circuit transmission line with shared towers may affect both circuits, while lightning risk varies among towers along the line. This study examines a 110 kV line in Guangxi, China, using lightning monitoring and operational records. Multi-wave-impedance models of representative tower types were developed in ATP-EMTP, and lightning withstand levels were determined using an insulator voltage–time characteristic criterion implemented in MODELS. An electrogeometric model was then used to estimate tower-level shielding-failure and backflashover trip-out rates, classify lightning risk, and propose a line surge arrester configuration. Thirty-three towers were identified for priority protection. In a model-based preliminary assessment, the estimated lightning-induced trip-out rate decreased from 9.747 to 2.579 trips per 100 km per year, a reduction of 73.54%. This case study provides a reference for differentiated lightning protection of similar lines.