Multi-Terminal Unsynchronized Fault Location for Distribution Networks Based on MM and SVR–PSO Hybrid Optimization
Dongmei Liu, Kai Zeng, Chengwei Luo, Tao Yuan, Peng Zeng, Ying Deng
Key points
From the paper's conclusion- Simulations of a 35 kV distribution network in the power systems computer-aided design/electromagnetic transients including DC (PSCAD/EMTDC) environment show that the method maintains high accuracy at different fault locations and under high transition resistance within the tested parameter range, demonstrating adaptability and reliability under these conditions.
Abstract
Complex distribution-network topologies limit the accuracy of traveling-wave fault location, because the zero-mode velocity decays nonlinearly while conventional double-ended methods still require synchronized clocks. A clock-offset-invariant multi-terminal scheme combining mathematical morphology (MM), support vector regression (SVR), and particle swarm optimization (PSO) is proposed to remove dependence on double-ended synchronization and constant zero-mode velocity. SVR first fits the nonlinear mapping between fault distance and zero-mode velocity to establish a velocity-decay predictor. Backward fault-current traveling waves measured at multiple nodes are then processed through cycle subtraction and dynamic-window denoising, constrained by the underlying zero-mode physics. A morphological-gradient operator identifies the line- and zero-mode arrival times, from which a cross-dispersion sum-of-products equation that eliminates zero-mode velocity is constructed. Preliminary auxiliary-node solutions are obtained, and PSO performs a global search by minimizing the residual between the measured modal time difference and the theoretical value obtained from the SVR-predicted velocity. Weighted fusion yields the final fault distance. Simulations of a 35 kV distribution network in the power systems computer-aided design/electromagnetic transients including DC (PSCAD/EMTDC) environment show that the method maintains high accuracy at different fault locations and under high transition resistance within the tested parameter range, demonstrating adaptability and reliability under these conditions.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- An Improved LSTM Method for Single-Phase Ground Fault Location in Distribution NetworksEnergies · 2026
- A Topology-Aware Neural Network for Fault Location With Missing MeasurementsarXiv · 2026
- Machine Learning and Deep Learning Techniques for Fault Location in Transmission LinesApplied Sciences · 2026
- Single-Ended Transmission Line Fault Location Based on Multi-Wavelet Time–Frequency Feature Fusion and a Residual Neural NetworkElectronics · 2026
- A Novel Distribution Network Reconfiguration Method with the Power Forecasting of DGsElectronics · 2026