Damping-Constrained Allocation of Frequency-Support Gains for Multiple VSC-HVDC Systems in a Synchronous Grid Using Port-Coupling Matrices and Safe Gain Maps

Jishuo Qin, Fan Li, Hanqing Liang, Binqi Ma, Taikun Tao, Guodong Guo

Key points

From the paper's conclusion
  • The gains selected from the map met the requirements in eight of nine intermediate operating conditions not used in its construction and, after one condition was added to the map, in all nine; the allocation agreed with a grid search within 0.0024 Hz of nadir.

Abstract

Voltage-source-converter HVDC stations that support the grid frequency take the support power back from the grid through the stations that regulate the DC voltage, unless an outside source supplies it. With several DC systems in one synchronous grid, the returned power acts on the electromechanical modes and can lower their damping. This paper sets the support gains under damping constraints. Each DC system is represented by a port-coupling matrix whose return shares distinguish in-grid stations, outside sources and DC capacitors. A necessary and sufficient passivity condition is derived for static gains, and the eigenvalue shifts yield a location rule for the sign of the damping contribution. The boundary of the safe gain set follows from the port characteristic equation, and sequential linear programs allocate the gains under constraints for damping, DC voltage, loss of one communication channel and parameter deviations. In a four-machine system with two DC systems and nine operating conditions, the allocation without damping constraints violated the 5% requirement in eight conditions (lowest damping ratio 1.48%), whereas the constrained allocation kept 5.03% and retained 67% to 100% of the nadir improvement. The gains selected from the map met the requirements in eight of nine intermediate operating conditions not used in its construction and, after one condition was added to the map, in all nine; the allocation agreed with a grid search within 0.0024 Hz of nadir. Electromagnetic-transient simulation confirmed the damping ratios within 0.40 percentage points, and in the New England 39-bus system the first-order shift reproduced the damping ratios with a mean error of 0.16 percentage points.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

Damping-Constrained Allocation of Frequency-Support Gains for Multiple VSC-HVDC Systems in a Synchronous Grid Using Port-Coupling Matrices and Safe Gain Maps — Science Skim