Grid-forming SVG DC-side hybrid capacitor series topology and capacity design method
Chao Gong, Yaohan Wang, Pengliang Xu, Haitao Liu, Yan Li
Key points
From the paper's conclusion- Methods A series hybrid DC-side topology combining supercapacitors and electrolytic capacitors with a bidirectional partial-power DC/DC converter is proposed.
Abstract
Introduction Grid-forming (GFM) static var generators (SVGs) require adequate DC-side energy storage to provide transient active-power support during grid-frequency disturbances. This study aims to reduce supercapacitor requirements while maintaining the transient support capability of GFM SVGs. Methods A series hybrid DC-side topology combining supercapacitors and electrolytic capacitors with a bidirectional partial-power DC/DC converter is proposed. An 800 V direct-connected all-supercapacitor system serves as the benchmark. An energy-equivalent synchronization method and a coordinated engineering sizing procedure are developed for realizable commercial-cell banks and the partial-power converter. Results Using identical 3.0 V/50 F cells, the benchmark and proposed systems require 297s1p and 75s1p supercapacitor banks, respectively. This represents a 74.75% reduction in supercapacitor cell count and the corresponding aggregate cell mass and geometrical volume relative to the specified benchmark. The selected DC/DC converter is rated at 2.114 kW, equivalent to 21.14% of the 10 kW SVG rating. Under the investigated consecutive disturbances with finite rates of change of frequency (RoCoF), the proposed system’s individual decline-stage peak support is approximately 1.52% lower than that of the benchmark. At the time of the benchmark system’s peak, the proposed system’s support is approximately 16.44% lower. The maximum normalized pointwise active-power difference reaches 30.23% during frequency recovery. The proposed system crosses the adopted 10% threshold 1 ms earlier; this is reported only as a diagnostic timing comparison. Discussion Under the investigated operating conditions, the proposed topology substantially reduces supercapacitor-cell requirements while using a converter rated at 21.14% of the SVG rating. It maintains comparable individual peak-support magnitudes and bidirectional energy-exchange characteristics, although the two systems have different peak timing and instantaneous active-power trajectories, particularly during frequency recovery.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Grid-Forming Static Power Generator with Coordinated Control of Two-Stage ConvertersSymmetry · 2026
- Coordinated capacitor-SVG reactive power compensation configuration for substations with high-penetration distributed photovoltaic integrationJournal of Renewable and Sustainable Energy · 2026
- Research on Grid-forming SLCC Control Based on Single-Synchronous Generator SimulationEngineering Research Express · 2026
- Capacity Ratio Estimation and Capability Assessment for Hybrid Grid-Following and Grid-Forming Converter SystemsEnergies · 2026
- Multi-Objective-Optimization-Based Optimal Sizing of Grid-Following SVG for Enhancing Transient Voltage Stability of Wind Farms Connected to Weak GridsElectronics · 2026
- Adaptive Transient Stability Control Strategy for GFL-GFM Hybrid Grid-Connected Systems Considering Power-Angle Difference PolarityElectronics · 2026