Coordinated Fault Ride-Through Control for a Hierarchically Connected VSC-HVDC System
Wei Wei, Peng Zhang, Zhiyong Zhang, Lilong Zhou, Pen Gu, Jianyu Zhou
Key points
From the paper's conclusion- CloudPSS simulation results demonstrate that the proposed control effectively utilizes the available transmission capability of the healthy converter, limits submodule capacitor overvoltage and excessive DC current rise, and mitigates second-harmonic active power oscillations under asymmetrical faults, thereby enhancing the FRT performance of the hierarchically connected VSC-HVDC system.
Abstract
As voltage-source converter-based high-voltage direct-current (VSC-HVDC) transmission systems evolve toward higher power ratings and voltage levels, a hierarchical configuration in which series-connected receiving-end converter units are connected to AC grids at different voltage levels introduces additional challenges in interlayer power coordination and fault ride-through (FRT). During a severe receiving-end AC voltage sag, the active power transfer capability of the faulted converter decreases markedly, whereas the sending-end input power cannot be reduced instantaneously. The resulting surplus power is absorbed by the submodule capacitors of the modular multilevel converter (MMC), leading to capacitor overvoltage. Under asymmetrical faults, pronounced second-harmonic active power oscillations also arise. To address these issues, control-oriented decoupling between the submodule capacitor voltage and the DC terminal voltage is first established, and a supplementary voltage reference is generated according to the average submodule capacitor voltage. The DC voltage references of the faulted and healthy converters are then coordinately adjusted to redistribute the DC voltage and active power between the receiving-end layers. When the healthy converter reaches its operating limit, an auxiliary DC current control is activated to achieve automatic sending-end power reduction. For asymmetrical faults, the second-harmonic active power component is further extracted from the AC- and DC-side active powers of the faulted MMC, and the resulting compensation term is superimposed on the capacitor overvoltage regulation term to form a composite supplementary voltage reference. CloudPSS simulation results demonstrate that the proposed control effectively utilizes the available transmission capability of the healthy converter, limits submodule capacitor overvoltage and excessive DC current rise, and mitigates second-harmonic active power oscillations under asymmetrical faults, thereby enhancing the FRT performance of the hierarchically connected VSC-HVDC system.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- A Virtual Resistance-Capacitance Control Strategy for Mitigating Consecutive Commutation Failures in Weak Receiving-End HVDC SystemsEnergies · 2026
- High-Symmetry Operation Control Algorithm for Receiving-End MMC Arm Current Oriented to Unidirectional Power TransmissionApplied Sciences · 2026
- System-Level Optimization of Hybrid Diode–Thyristor Fault Current Limiters for Multi-Terminal HVDC ProtectionEnergies · 2026
- Unbalanced Fault Ride-Through in Grid-Forming Modular Multilevel ConvertersIEEE Journal of Emerging and Selected Topics in Power Electronics · 2026
- High-Frequency oscillation mechanism and suppression strategy for renewable energy integration via VSC-HVDC systemsInternational Journal of Electrical Power & Energy Systems · 2026
- An Advanced Dual Energy Control with Energy Dissipation Strategy to Enhance Fault Ride-Through in Offshore Wind MMC-HVDC SystemsEnergies · 2026