Design Recommendation and Site Implementation of High‐Voltage Double‐Y–Type Harmonic Filter Bank for Utility Substation: Real Industrial Site Experience
Ashish Chandra, Mukhtiar Singh
Key points
From the paper's conclusion- Unlike previous studies that primarily rely on simulation, the proposed methodology is validated through practical implementation and field measurements at an operating 132/33‐kV utility substation, demonstrating its applicability under real network conditions.
Abstract
This research addresses power quality issues in a 132/33‐kV utility substation, specifically harmonic generation, low power factor, and poor voltage profile. To address these problems, a high‐voltage Y‐Y–type harmonic filter (HF) is proposed. This filter mitigates harmonics and improves power factors and voltage profile. Thorough analysis and simulation are conducted using ETAP, PSCAD, and Power Quality Analyzer software to ensure accuracy and reliability. The HF design phase accounts for the effects of transformer tapping and series reactor impedance on inrush current suppression. Load flow analysis is performed considering different transformer loading patterns. The resulting power factor and voltage profile waveforms are evaluated before and after the HF installation. The HF design aligns with the IEEE and IEC standards. In addition, this research introduces the concept of unbalanced current protection to enhance system stability and reliability. This comprehensive approach further strengthens the proposed HF as a holistic solution. To validate the effectiveness of the proposed solution, the implemented HF is deployed in a practical utility distribution substation. Real‐world field measurements confirm the effectiveness of the proposed solution, demonstrating its positive impact on power quality. Unlike previous studies that primarily rely on simulation, the proposed methodology is validated through practical implementation and field measurements at an operating 132/33‐kV utility substation, demonstrating its applicability under real network conditions.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- From Power Quality Monitoring to Reactive Power Compensation: A Measurement-Based Framework for Sizing Passive Compensators in Low-Voltage InstallationsEnergies · 2026
- A harmonic–economic optimization framework for filter design and placement in active distribution systemsInternational Journal of Emerging Electric Power Systems · 2026
- Intelligent Power Quality Correction Using Predictive Models and Metaheuristic OptimizationEPJ Web of Conferences · 2026
- Waveform Analysis of Non-Sinusoidal Electrical Signals Using Cubic Spline InterpolationEng · 2026
- Input Current Harmonic Suppression in a 12-Pulse Delta/Wye-Connected System Using a Novel Passive Auxiliary CircuitEnergies · 2026
- Power quality enhancement using fractional order type-2 fuzzy SHAF optimized with hPSOFA algorithmScientific Reports · 2025