Energies

From Power Quality Monitoring to Reactive Power Compensation: A Measurement-Based Framework for Sizing Passive Compensators in Low-Voltage Installations

Dawid Buła, Dariusz Grabowski, Tadeusz Białoń, Roman Niestrój

Computational

Key points

From the paper's conclusion
  • The results demonstrate that high-resolution monitoring data can support practical compensator design and reduce reactive power exchange, thereby improving operating conditions in low-voltage distribution systems.

Abstract

High-resolution power quality monitoring can support energy-saving actions in low-voltage installations by providing data for engineering decisions aimed at reducing unnecessary reactive power flow and associated network losses. This paper presents a measurement-based framework for sizing passive reactive power compensators composed of switchable capacitor and reactor sections. Unlike conventional sizing methods based directly on measured reactive power values, the proposed method uses 1-s active and reactive power profiles and evaluates each candidate configuration with a network model that accounts for voltage-dependent compensator characteristics, transformer influence, controller averaging, and minimum switching intervals. The sizing task is formulated as a binary optimization problem minimizing uncompensated reactive energy. A brute-force search is used as a benchmark, while a genetic algorithm serves as a practical offline optimization tool. The framework is demonstrated for an exemplary phase using measurements recorded in an office-type low-voltage installation with unequal phase load profiles. For a five-day working profile, the optimized eight-section compensator reduced reactive energy from 473.1 kvarh to 34.0 kvarh, corresponding to a compensation efficiency of 92.8% and an increase in the average power factor from 0.909 to 0.997. A six-section design achieved a comparable efficiency of 92.0% while requiring 27% fewer switching operations, highlighting the trade-off between compensation performance and implementation complexity. Validation using independent load profiles confirmed robust performance, with efficiency differences below 1.4 percentage points. The results demonstrate that high-resolution monitoring data can support practical compensator design and reduce reactive power exchange, thereby improving operating conditions in low-voltage distribution systems.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers