Simulation research on corrosion state detection of tower grounding grids based on magnetic field response
Weiwen Liao, Peng Zhang, Di Xing, Naihuan Liu, Jinxi Wu
Key points
From the paper's conclusion- Therefore, peak attenuation, average value, waveform area, local valley, and waveform asymmetry can be used as corrosion identification features.
Abstract
Tower grounding grids buried in soil are prone to corrosion, section thinning, and local breakage, which may affect grounding safety. To support non-excavation detection, this paper studies corrosion identification based on surface magnetic field response. A coupled magnetic-field and circuit simulation model is built, and corrosion is represented by effective section reduction and a high-resistance oxide layer. The effects of uniform corrosion, break-point corrosion, and multiple-conductor proximity on surface magnetic flux density are analyzed. The results show that uniform corrosion mainly causes overall amplitude attenuation, while break-point corrosion leads to local waveform distortion and low-value areas. Therefore, peak attenuation, average value, waveform area, local valley, and waveform asymmetry can be used as corrosion identification features. The study provides a reference for corrosion detection and condition assessment of tower grounding grids. A supplementary comparison with controlled tank and field-like magnetic traces, together with anti-interference and path-deviation cases, is added to clarify the practical applicability of the simulated waveform features.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Research on corrosion detection criteria for tower grounding grids based on corrosion characteristics and magnetic field responseJournal of Physics: Conference Series · 2026
- Aplicación de sondeos eléctricos como ensayos no destructivos para la evaluación de corrosión en elementos de aceroConcienciaDigital · 2026
- A Multiple-Fault Diagnosis Method for Non-Uniform Grounding Grids Based on Dynamic Topology TearingInfrastructures · 2026
- Analysis of grounding characteristics of single-direction extended auxiliary grounding grids for transmission towersJournal of Physics: Conference Series · 2026
- Electric-Field-Based Reconstruction of Transmission-Line Galloping Characteristics Using an Arc-Length ConstraintEnergies · 2026
- Effect of High‐Speed Railway Operational Conditions on the Dynamic AC Corrosion Behavior and Mechanisms of Pipeline SteelMaterials and Corrosion · 2026