Infrastructures

A Multiple-Fault Diagnosis Method for Non-Uniform Grounding Grids Based on Dynamic Topology Tearing

Rui Zhou, Xiaobin Cao, Xinyu Shi, Ruifang Li

Key points

From the paper's conclusion
  • Three alternative solvers achieved 0.3801–0.4282 in 120.74–129.47 s.

Abstract

Corrosion and conductor breaks in grounding grids can compromise the safe dissipation of substation fault currents. To diagnose these faults using only a limited number of accessible nodes, this study groups frequencies and selects reference-port impedances based on the distribution of injected currents throughout the grounding grid at different frequencies. The topology-tearing method retains all nodal voltages and employs equivalent sources to approximate the effects of currents in fixed branches. For a grounding grid comprising 49 branches, this method reduces the number of unknowns from 79 at low frequencies to 47 at high frequencies. The proposed hybrid algorithm (ERS-DBO-SQP) augments dung beetle optimization with reflection and scattering moves during stagnation and uses sequential quadratic programming for local refinement. In the selected timed run on this grid, ERS-DBO-SQP achieved a geometric mean of sensitivity and specificity of 0.8563 in 91.25 s of solver time. Three alternative solvers achieved 0.3801–0.4282 in 120.74–129.47 s. Numerical simulations, CDEGS simulations, and field tests demonstrate that the proposed method can effectively identify corrosion and conductor-break faults with high diagnostic accuracy.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

A Multiple-Fault Diagnosis Method for Non-Uniform Grounding Grids Based on Dynamic Topology Tearing — Science Skim