Energy use for ventilation in dwellings – Simulation comparison between plate and rotary heat exchanger in ventilation systems

Dennis Johansson, Hans Bagge

Computational

Key points

From the paper's conclusion
  • This is substantial but can be reduced by in the magnitude of 80 % by a heat recovery between exhaust and supply air, either in the type of a plate heat exchanger or with a rotary wheel between the two air streams.

Abstract

Typically, in mid Sweden, the heating energy loss of ventilation air is 0.35 l/(s·m 2 floor) · 1.2 kg/m 3 · 1 kJ/(kg · °C) · 100 000 °C · h = 42 kWh/m 2 floor. This is substantial but can be reduced by in the magnitude of 80 % by a heat recovery between exhaust and supply air, either in the type of a plate heat exchanger or with a rotary wheel between the two air streams. The rotary wheel normally has the advantage of slightly higher temperature efficiency and in normal conditions no problem with frost accumulation, but will to a certain extent also recover moisture. If moisture determines the needed airflow, a slightly higher airflow is needed compared to a plate heat exchanger without moisture recovery. This paper presents a simulation comparison between these two types of heat exchangers regarding the total heating needed in a building including the heating of ventilation air. It will be based on numerical models of the heat exchangers, the power balance of the building and moisture supply in the building for different variations of parameters regarding moisture production and performance as well as use of the building for Swedish outdoor climates. The typical moisture supply will be based om measurements in over approximately 200 Swedish dwellings.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers