Sensitivity of Heating Energy Demand to Indoor Temperature, Effective Air-Change Rate, and Climate: A TRNSYS Case Study Supporting Sustainable Operation of a Multi-Apartment Building
Marija Živić, Matej Đuranović, Antun Barac, Katica Šimunović
Key points
From the paper's conclusion- Increasing the indoor temperature from 18 to 26 °C increased seasonal demand by 432.63–525.32 MWh, while increasing the effective air-change rate from 0.30 to 0.70 h−1 increased it by 182.67–296.55 MWh.
Abstract
Building heating energy demand is influenced by indoor temperature, air exchange, and climatic conditions. This study examines the individual and combined effects of these parameters on a district-heated multi-apartment residential building in Osijek, Croatia. A TRNSYS model was evaluated using measured space-heating consumption for the analysed period from October 2024 to April 2025 and representative TMYx weather data. In the model, air exchange was represented by an effective air-change rate accounting for both uncontrolled air infiltration through the building envelope and natural ventilation associated with occupant window opening. The measured seasonal consumption was 666.16 MWh, while the model predicted 670.61 MWh, resulting in a deviation of 0.67%. The model was then used for a full-factorial analysis including nine indoor temperatures from 18 to 26 °C, nine effective air-change rates from 0.30 to 0.70 h−1, and six Croatian locations, giving 486 simulation scenarios. Under reference conditions, heating demand in Zadar and Split was 44.05% and 50.93% lower than in Osijek/Čepin. Increasing the indoor temperature from 18 to 26 °C increased seasonal demand by 432.63–525.32 MWh, while increasing the effective air-change rate from 0.30 to 0.70 h−1 increased it by 182.67–296.55 MWh. The analysis also showed a positive interaction between indoor temperature and effective air-change rate. For the analysed building, the results can support more sustainable energy use by informing energy-efficient building operation and district-heating demand planning, while the reported numerical sensitivities remain specific to the case-study building.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Impact of Airflow Modelling Approaches on Residential Building Energy Demand Under Different Climatic ConditionsBuildings · 2026
- Future Temperature-Induced Heating Demand in Buildings: Regional Patterns and Renewable Energy Implications in PolandEnergies · 2026
- Feedback Effects of Air-Conditioning Anthropogenic Heat on Cooling Energy Consumption in Residential Buildings: A CFD–EnergyPlus Co-Simulation StudyBuildings · 2026
- Thermal comfort in office-to-residential adaptive reuse: A Swedish case studyE3S Web of Conferences · 2026
- Differential Effects of Building Design Parameters on Building Energy Performance in the Western Sichuan Plateau: An Explainable Machine Learning AnalysisBuildings · 2026
- DETRANS potential model for energy-and power demand savings in the Norwegian building stockE3S Web of Conferences · 2026