Wraparound Heat Exchangers and Passive Desiccant Wheels for Improving Dehumidification and Reducing Reheat: Evidence and Limitations
Łukasz Stefaniak, Juliusz Jerzy Walaszczyk, Marderos Ara Sayegh
Key points
From the paper's conclusion- Compared with overcooling and reheat, the coil load fell by 12–30%, and the energy use fell by up to 50% with heat exchangers, and the energy use fell by 33–76% with passive wheels; compared with the same unit without the device, the measured COP or EER changed by from −5% to +48%.
Abstract
Air conditioners in humid climates often remove too little moisture, and the usual remedy, overcooling followed by reheat, uses extra energy. Wraparound devices around the cooling coil of a vapor-compression unit can increase dehumidification without new refrigeration equipment. This review compares sensible wraparound heat exchangers, such as heat pipes, which precool the air before the coil and reheat it after the coil, with passive desiccant wheels, which move water vapor from the cold air leaving the coil to the air entering it. Twenty-five primary studies and four manufacturer documents were analyzed, together with the coil models and performance metrics used. Both device types lowered the sensible heat ratio by 0.04–0.12 for a heat-pipe retrofit and by 0.14–0.27 for passive wheels. Compared with overcooling and reheat, the coil load fell by 12–30%, and the energy use fell by up to 50% with heat exchangers, and the energy use fell by 33–76% with passive wheels; compared with the same unit without the device, the measured COP or EER changed by from −5% to +48%. Differences in the reference system, efficiency definition and airflow appear to explain much of this spread. The evidence for passive wheels is insufficient. It rests on six single-unit tests by three research groups and on manufacturer data, and no long-term monitoring was found. A test and reporting method at the same supply state is proposed, and long-term monitoring is suggested to close these gaps.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- A TRNSYS-based parametric study of building ventilation systems incorporating Rotary Heat Recovery WheelsApplied Thermal Engineering · 2026
- Load-Adaptive Operational Control of an Indirect Evaporative Cooling System for Coordinated Energy and Water Use in a Modular Data Center in a Cold RegionBuildings · 2026
- Experimental study on performance improvement and energy savings of split-type air conditioning system using direct evaporative cooling in hot Iraqi climateInternational Communications in Heat and Mass Transfer · 2026
- Energy-Efficient Design Optimization of a Multistage Indirect Evaporative Cooler for Sustainable Cooling in Hot and Dry ClimatesSustainability · 2025
- Energy use for ventilation in dwellings – Simulation comparison between plate and rotary heat exchanger in ventilation systemsE3S Web of Conferences · 2026
- Experimental study on the performance of a two-stage heat pump drying system coupled with rotary dehumidification and total heat recoveryCase Studies in Thermal Engineering · 2026