Digitally assisted HVAC design and performance verification for a rapid diagnostic test production room
Rizal Kusaeri, Windy Hermawan Mitrakusuma, Risna Pamungkas
Key points
From the paper's conclusion- This study evaluated a digitally assisted design-to-verification workflow for Ruang Kering 2 (Dry Lab 2) at PT Pakar Biomedika Indonesia, with URS limits of temperature <26 °C, relative humidity <30%, and 6-20 It 1 air changes.
Abstract
Environmental control in a rapid diagnostic test (RDT) production room requires an HVAC system that converts process requirements into quantitative design criteria and verifies them after installation. This study evaluated a digitally assisted design-to-verification workflow for Ruang Kering 2 (Dry Lab 2) at PT Pakar Biomedika Indonesia, with URS limits of temperature <26 °C, relative humidity <30%, and 6-20 It 1 air changes. URS and existing-condition data supported cooling-load and dehumidification calculations, equipment selection, installation, TAB, and environmental monitoring. The calculated room cooling load was 30,436 Btu/h, the required moisture-removal capacity was 4.314 kg/h, and the total thermal-load reference was 61,162 Btu/h. The selected cooling unit and dehumidifier provided nominal capacity margins of 40.4% and 4.3%, respectively. Following TAB, the measured supply airflow was 1,146 mVh, corresponding to 19.93 h~i. One-month at-rest monitoring recorded temperatures of 21-25.2 °C and relative humidity of 20-28%, all within the URS limits. Nominal equipment capacity alone did not establish environmental compliance; field TAB and monitoring were required to verify actual performance. Electrical energy consumption was outside the original measurement scope and was not quantified.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- "DC-HVAC-DT23: Data Center Cooling Telemetry and Probabilistic Surrogate Rollout Dataset"IEEE DataPort · 2026
- Energy-efficient HVAC operation in pharmaceutical cleanrooms through fan frequency adjustment during requalificationE3S Web of Conferences · 2026
- Load-Adaptive Operational Control of an Indirect Evaporative Cooling System for Coordinated Energy and Water Use in a Modular Data Center in a Cold RegionBuildings · 2026
- Validation of a dynamic evaporation technique for generating isoflurane/air gas mixtures standards to calibrate anesthetic gas monitors.Scientific reports · 2026
- Experimental study on advanced indirect evaporative cooling and desiccant dehumidification systems for agricultural greenhousesInternational Communications in Heat and Mass Transfer · 2025
- Development and Thermal Validation of a Portable Guarded Hot Box for Steady-State Window U-Value MeasurementsJournal of Physics: Conference Series · 2026