Digitally assisted HVAC design and performance verification for a rapid diagnostic test production room

Rizal Kusaeri, Windy Hermawan Mitrakusuma, Risna Pamungkas

Key points

From the paper's conclusion
  • This study evaluated a digitally assisted design-to-verification workflow for Ruang Kering 2 (Dry Lab 2) at PT Pakar Biomedika Indonesia, with URS limits of temperature <26 °C, relative humidity <30%, and 6-20 It 1 air changes.

Abstract

Environmental control in a rapid diagnostic test (RDT) production room requires an HVAC system that converts process requirements into quantitative design criteria and verifies them after installation. This study evaluated a digitally assisted design-to-verification workflow for Ruang Kering 2 (Dry Lab 2) at PT Pakar Biomedika Indonesia, with URS limits of temperature <26 °C, relative humidity <30%, and 6-20 It 1 air changes. URS and existing-condition data supported cooling-load and dehumidification calculations, equipment selection, installation, TAB, and environmental monitoring. The calculated room cooling load was 30,436 Btu/h, the required moisture-removal capacity was 4.314 kg/h, and the total thermal-load reference was 61,162 Btu/h. The selected cooling unit and dehumidifier provided nominal capacity margins of 40.4% and 4.3%, respectively. Following TAB, the measured supply airflow was 1,146 mVh, corresponding to 19.93 h~i. One-month at-rest monitoring recorded temperatures of 21-25.2 °C and relative humidity of 20-28%, all within the URS limits. Nominal equipment capacity alone did not establish environmental compliance; field TAB and monitoring were required to verify actual performance. Electrical energy consumption was outside the original measurement scope and was not quantified.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers