Energy-efficient HVAC operation in pharmaceutical cleanrooms through fan frequency adjustment during requalification

Arief Danar Kusumah, Apip Badarudin, Risna Pamungkas

Key points

From the paper's conclusion
  • The results indicate that requalification-based adjustment can maintain cleanroom requirements while identifying potential reductions in fan operating demand.

Abstract

Pharmaceutical cleanrooms require HVAC systems that maintain specified air change rates and thermal conditions while avoiding unnecessary fan energy demand. This study evaluates the requalification and potential reduction in fan operating demand of three air-handling units (AHU F2.5, F2.6, and F2.7) following HEPA H13 filter replacement. The evaluation focused on air change rate (ACH), supply-duct pressure set point (Px), fan inverter frequency, temperature, and relative humidity (RH). Supply airflow was measured using a balometer, while Px and inverter frequency data were obtained from the building automation system (BAS). Testing, adjusting, and balancing were performed to establish compliant operating conditions. All 16 evaluated areas achieved final ACH values of 10.00–18.39 h −1 . Px set points decreased from 480 to 380 Pa for F2.5, 180 to 150 Pa for F2.6, and 560 to 245 Pa for F2.7. Inverter frequencies changed by –18.60%, +7.14%, and –8.45%, respectively. Room temperatures remained at 22-23°C and RH at 46–54%, within URS limits. The results indicate that requalification-based adjustment can maintain cleanroom requirements while identifying potential reductions in fan operating demand.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers