Influence of Airflow Rate and Relative Humidity on the Thermal Efficiency and Energy Consumption of Underground Mine Ventilation Systems
Maria-Isabela Cașotă, Dan Codruț Petrilean
Key points
From the paper's conclusion- This study evaluates the influence of airflow rate and relative humidity on the thermal and energetic performance of an underground ventilation system using a transparent simulation-based dataset of 90 operating scenarios.
Abstract
Underground mine ventilation is simultaneously a safety-critical service and a major electrical load. This study evaluates the influence of airflow rate and relative humidity on the thermal and energetic performance of an underground ventilation system using a transparent simulation-based dataset of 90 operating scenarios. Airflow rate varied from 8 to 26 m³/s, relative humidity from 45% to 90%, inlet air temperature from 24°C to 34°C, and pressure drop from 650 to 1550 Pa. Fan electrical power was calculated from airflow, pressure drop and fan efficiency, while thermal effectiveness and a non-regulatory heat-stress proxy were represented through physically motivated response functions. Descriptive statistics, Pearson correlation, multiple linear regression and one-way ANOVA were applied. The analysis illustrates the central energy–thermal trade-off: increasing airflow improves the simulated thermal response but increases fan power, while higher humidity degrades thermal conditions. The framework is intended for methodological screening and subsequent validation with measured mine data.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Numerical Investigation of Multifield Coupling in Surrounding Rock of Deep Roadways Under High-Temperature ConditionsMining · 2026
- Quantifying the Thermal and Energy Impacts of Air Infiltration in a Hot-Humid Educational Building: A Sensitivity Analysis Using a Field-Evaluated EnergyPlus ModelBuildings · 2026
- Influence of Ambient Temperature Variation on the Energy Efficiency and Thermal Performance of Cooling Systems in Critical Environments: A Thermodynamic Analysis of Mining Facilities and Data CentersMining Revue · 2026
- Effect of an insulating shotcrete layer on the transient thermal response of a mine roadway under time-varying surrounding-rock temperaturesJournal of Thermal Analysis and Calorimetry · 2026
- Improving Airflow Network Models of Natural Ventilation: Geometry-Specific Pressures and Fluctuation CorrectionsarXiv · 2026
- A Loop-Space Embedded Optimization Framework for Energy-Efficient Underground Mine Ventilation NetworksProcesses · 2026