Unified Fault Ride‐Through Control of DFIG Wind Turbines via Adaptive Flux Damping and Disturbance‐State Separation
Taiguo Li, Wanyin Gong, Caixia Tao, Heping Qu
Key points
From the paper's conclusion- Simulation results under low‐voltage ride‐through (LVRT), high‐voltage ride‐through (HVRT), and cascading fault conditions show that the proposed method effectively limits rotor current, torque oscillation, and DC‐link voltage deviation to within 0.8, 0.6, and 0.02 p.u., respectively, demonstrating improved overall fault ride‐through performance.
Abstract
With the increasing penetration of renewable energy, doubly fed induction generator (DFIG) systems are increasingly exposed to low‐high voltage cascading disturbances rather than isolated voltage events. Such disturbances cause stator flux components to be inherited and superimposed across stages, leading to intensified rotor current surges and aggravated DC‐link energy fluctuations. To address this issue, a unified transient model of the DFIG under cascading faults is established to reveal the residual flux inheritance mechanism. Based on this mechanism, a mechanism‐oriented full‐process coordinated control framework is proposed for the rotor‐side converter (RSC) and grid‐side converter (GSC). The RSC integrates active demagnetization with adaptive reactive power regulation to suppress residual‐flux‐induced electromagnetic transients, whereas the GSC employs linear active disturbance rejection control (LADRC) with adaptive fusion of fast and slow linear extended state observers (LESOs) to regulate the DC‐link voltage. A stator‐flux‐error‐based cross‐converter compensation mechanism further couples the transient actions of the RSC and GSC, so that flux damping, reactive power regulation, and DC‐link energy balancing are coordinated throughout the cascading fault process. Simulation results under low‐voltage ride‐through (LVRT), high‐voltage ride‐through (HVRT), and cascading fault conditions show that the proposed method effectively limits rotor current, torque oscillation, and DC‐link voltage deviation to within 0.8, 0.6, and 0.02 p.u., respectively, demonstrating improved overall fault ride‐through performance.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Dynamic active torque coordination strategy for torsional vibration suppression in wind turbines during grid fault recoveryInternational Journal of Electrical Power & Energy Systems · 2026
- Active Fault-Tolerant Control for DFIG-Based Wind Energy Conversion Systems Using a Sensor FDI and a Novel Reconfiguration FrameworkEnergies · 2026
- Improved linear active disturbance rejection control for mitigating subsynchronous control interaction in DFIG systems.ISA transactions · 2026
- Electromechanical and Structural Loading Effects of Virtual Synchronous Generator Control in Doubly Fed Induction Generator Wind TurbinesElectronics · 2026
- DFIG Low‐Voltage Ride‐Through in Weak Grids: Rotor Overcurrent, PLL Effects, and Crowbar BoundariesInternational Journal of Energy Research · 2026
- Adaptive Damping Control for Stability Enhancement of Grid-Following Converters Based on q-Axis Voltage Magnitude FeedbackEnergies · 2026