CFD Assessment of Thermal Comfort and Heating Demand in Courtrooms Under Envelope Retrofit Scenarios

Cătălin Ciprian Vulpe, Florin-Emilian Țurcanu, Valeriu-Sebastian Hudișteanu, Cristian-Nelu Cherecheș, Claudiu Romila, Cătălin Onuțu, Dragoș Ungureanu, Adrian Alexandru Șerbănoiu,

Key points

From the paper's conclusion
  • We combined infrared thermography with steady CFD including surface radiation and a coupled envelope (OpenFOAM, cross-checked with Ansys Fluent) to assess window replacement and wall insulation in three courtrooms in Iași, Romania, at −18 °C outdoors.

Abstract

Courtrooms are tall rooms in which cold glazing, radiator plumes and stratification shape winter comfort. We combined infrared thermography with steady CFD including surface radiation and a coupled envelope (OpenFOAM, cross-checked with Ansys Fluent) to assess window replacement and wall insulation in three courtrooms in Iași, Romania, at −18 °C outdoors. The model was verified on three meshes and tested against a downdraught correlation and measured air temperatures; after calibration of the unknown heat input, it underestimated the air temperature of two further periods by 1.2–1.7 K. The mean PMV stayed between −0.07 and 0.04 and the mean draught rate below 8%, but the radiators did not prevent downdraught: the ankle-level draught rate in the first seat row reached 24–29%, above the 20% limit of category B, and 18–24% after wall insulation. Window replacement cut the transmission loss by 13–21%, and, with wall insulation, by 39–75%, after which ventilation becomes the largest loss. Supply air at 12 °C after heat recovery caused draught in a fifth of the occupied zone. Envelope retrofit should therefore come with demand-controlled ventilation, enthalpy recovery and supply air reheated close to room temperature.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

CFD Assessment of Thermal Comfort and Heating Demand in Courtrooms Under Envelope Retrofit Scenarios — Science Skim