CFD Assessment of Thermal Comfort and Heating Demand in Courtrooms Under Envelope Retrofit Scenarios
Cătălin Ciprian Vulpe, Florin-Emilian Țurcanu, Valeriu-Sebastian Hudișteanu, Cristian-Nelu Cherecheș, Claudiu Romila, Cătălin Onuțu, Dragoș Ungureanu, Adrian Alexandru Șerbănoiu,
Key points
From the paper's conclusion- We combined infrared thermography with steady CFD including surface radiation and a coupled envelope (OpenFOAM, cross-checked with Ansys Fluent) to assess window replacement and wall insulation in three courtrooms in Iași, Romania, at −18 °C outdoors.
Abstract
Courtrooms are tall rooms in which cold glazing, radiator plumes and stratification shape winter comfort. We combined infrared thermography with steady CFD including surface radiation and a coupled envelope (OpenFOAM, cross-checked with Ansys Fluent) to assess window replacement and wall insulation in three courtrooms in Iași, Romania, at −18 °C outdoors. The model was verified on three meshes and tested against a downdraught correlation and measured air temperatures; after calibration of the unknown heat input, it underestimated the air temperature of two further periods by 1.2–1.7 K. The mean PMV stayed between −0.07 and 0.04 and the mean draught rate below 8%, but the radiators did not prevent downdraught: the ankle-level draught rate in the first seat row reached 24–29%, above the 20% limit of category B, and 18–24% after wall insulation. Window replacement cut the transmission loss by 13–21%, and, with wall insulation, by 39–75%, after which ventilation becomes the largest loss. Supply air at 12 °C after heat recovery caused draught in a fifth of the occupied zone. Envelope retrofit should therefore come with demand-controlled ventilation, enthalpy recovery and supply air reheated close to room temperature.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Assessment and Improvement Strategies for the Winter Indoor Thermal Environment of Temporary Construction-Site Buildings in Cold RegionsBuildings · 2026
- Optimizing Window Installation Depths to Reduce Thermal Bridging in Hot-Climate Building EnvelopesBuildings · 2026
- When Is a Room Error an HVAC Error? A Task-Aware Evaluation Framework for Floor-Plan Room Reconstruction Using Thermal-Zone Proxies and Design LoadsBuildings · 2026
- Computational Fluid Dynamics-Based Quantitative Assessment and Performance Optimization of Thermal Comfort in Hyper-Arid Climate Office BuildingsSustainability · 2025
- HEAT TRANSFER AND CONVECTION ANALYSIS FOR THERMAL COMFORT OPTIMIZATION IN AN OFFICE WITH GLASS PARTITION ZONINGRevista Foco · 2026
- Zur Akustik und Energieeffizienz von Wandlüftern mit WärmerückgewinnungBauphysik · 2026