Key points
From the paper's conclusion- A fixed wall-based room generator and learned room outputs were evaluated on 297 CubiCasa5K plans and 122 CVC-FP scans against functional spaces, a wall-derived zone proxy (geometric continuity, not engineered HVAC zoning) and simplified zone design loads; 60 plans were simulated in EnergyPlus as a shared-input consistency check.
Abstract
Floor-plan room reconstruction is usually scored against annotated functional spaces, whereas building energy modeling and heating, ventilation and air-conditioning (HVAC) design use zones and zone loads. This study develops an evaluation framework to determine how the evaluation target and load-allocation rule change conclusions about reconstruction quality. A fixed wall-based room generator and learned room outputs were evaluated on 297 CubiCasa5K plans and 122 CVC-FP scans against functional spaces, a wall-derived zone proxy (geometric continuity, not engineered HVAC zoning) and simplified zone design loads; 60 plans were simulated in EnergyPlus as a shared-input consistency check. Scoring the same output against proxy zones raised its matched share from 57.6% to 77.3%. Under single-candidate allocation, closing and annotated door lines raised heating-load agreement within ±20% from 72.7% to 80.6%, whereas detected door lines added 0.5 points; these gains persisted under joining-rule changes. Raster2Seq had the highest room F1 but lower load agreement than closing alone (69.9% vs. 76.2%); this comparison was not robust to pooling or redistributing loads using the reference zones. For wall-based conditions, simplified–EnergyPlus verdict agreement was 98–99% for heating and 94–97% for cooling. Energy-workflow evaluations should report the zone definition, allocation rule and door-input provenance alongside room F1.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Orientation-Specific Multi-Objective Optimization of Building Envelopes for University Library Reading Spaces: A Design Framework Based on Field-Calibrated Simulation and Hierarchical Decision-MakingApplied Sciences · 2026
- Explainable AI for Multiobjective Design Decisions in University Teaching BuildingsBuildings · 2026
- Heating Buildings Only When Needed: A Data-Driven Based Framework for Comfort-Aware HVAC SchedulingBuildings · 2026
- PR-Unet: A Pressure-Conditioned Residual U-Net for Indoor Airflow and Temperature Prediction in Hospital WardsBuildings · 2026
- Online Identification Can Replace a Floor-Plan Prior on Unseen BuildingsarXiv · 2026
- A refined theoretical method for reducing overestimation in building-level design cooling load derived from temporal misalignment of room-level design cooling loadsResults in Engineering · 2026