Optimal Load Allocation Among Units in Large Hydropower Stations Based on an Optimal Load Allocation Table

Faying Gu, Yongsheng Liu, Yongwei Han, Qingsong Jiang, Enzhong Wang, Hongxu Liu, Wenji Wang, Shuai Jin,

Key points

From the paper's conclusion
  • Moreover, it can obtain the optimal load allocation combination of units under various operating conditions, reducing the monthly average water consumption rate of the power station by 5.03% and the low-efficiency operation time of units by 61.37% during the dry season and reducing the monthly average water consumption rate of the power station by 1.57% and the low-efficiency operation time of uni

Abstract

To address the new dispatching characteristics and increasingly complex operational requirements of hydropower station operation, including large installed capacity, large-scale units, and prohibited operating zones for multiple types of units, an intra-plant economic operation model is established with the objectives of safe, stable, and economic operation, thereby achieving optimal load allocation among units under various operating conditions. The optimal output ranges of individual units under different heads are analyzed, the load allocation rules of the station are investigated, and the intra-plant economic operation model is formulated. Based on this model, an optimal load allocation table is designed, and the optimal load allocation result tables for different loads, heads, and start–stop combinations are proposed to guide real-time intra-plant economic dispatch. The application at Maerdang Hydropower Station demonstrates that the optimization model can reasonably determine the start–stop sequence and the number of units in operation according to real-time load commands, and can provide real-time start-up and shut-down recommendations. Moreover, it can obtain the optimal load allocation combination of units under various operating conditions, reducing the monthly average water consumption rate of the power station by 5.03% and the low-efficiency operation time of units by 61.37% during the dry season and reducing the monthly average water consumption rate of the power station by 1.57% and the low-efficiency operation time of units by 64.71% during the flood season, thereby ensuring high-efficiency unit operation and improving the economic benefits of the station.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers