Output-Interval-Indexed Adaptive Pickup Current Settings for Inverse-Time Overcurrent Protection in Distribution Networks with High Shares of Inverter Interfaced Renewable Generation

Jun Li, Haotian Ge, Jiuming Zhong, Haonan Jiang

Key points

From the paper's conclusion
  • In a 1 s photovoltaic profile, the switching logic reduces setting changes from 1140 to 98 per day, with no invalid settings for latencies up to 1 s.

Abstract

At high penetration levels, the fault currents of inverter-interfaced distributed generators (IIDGs) depend on their pre-fault output and control state, so the operating times and coordination time intervals (CTIs) of inverse-time overcurrent relays change with the output. This paper proposes an adaptive pickup-current setting method indexed by pre-fault output intervals. Fault-current models with low-voltage ride-through (LVRT) and current limiting are established. The relay currents are written in a current-distribution-factor form, and a closed-form condition shows when IIDG infeed compresses the CTI below its limit. Preliminary pickups preserve the baseline sensitivity; load security gives the lower bound, local-zone sensitivity and backup pickup give the upper bound, and a CTI step raises pickups where coordination requires it. Time multipliers and the standard inverse curve are not changed, and the monotone iteration is shown to return the smallest feasible pickups. The settings are stored in an offline table and switched online with hysteresis, a confirmation time and a validity guard. In the main case (70% penetration), fixed settings remain selective; the method keeps the local operating times of the middle- and end-section relays at their baseline values and narrows the CTI range between the two downstream relays by 50.8%. In an upstream-infeed weak-grid case, fixed settings reduce the CTI to 0.165 s, whereas the setting table keeps it at or above 0.200 s. In a 1 s photovoltaic profile, the switching logic reduces setting changes from 1140 to 98 per day, with no invalid settings for latencies up to 1 s.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

Output-Interval-Indexed Adaptive Pickup Current Settings for Inverse-Time Overcurrent Protection in Distribution Networks with High Shares of Inverter Interfaced Renewable Generation — Science Skim